Advanced Configuration
March 2017
9. Ensure that the Enable check box is selected.
10.In the Value Unit field choose a suitable unit to match the input source.
11.In the Value Range pane, enter the parameter values that correspond to the analog input values
4 and 20 mA. You can specify any value as long as the 20 mA value is higher than the 4 mA value. If
the measured value goes outside the range values, the analog input enters alarm mode.
12.Use the Advanced button in case you would like to configure Filter Factor and Current Limits.
By setting a Filter Factor you can suppress spurious fluctuations in the analog input signal. A value
between 0 and 1 can be used. The default value is 0.1. A higher value means less filtering.
The Current Limits define the lower and upper limits of the input currents. Outside this range an error will
be indicated. The current limits should correspond to the error limits of connected instruments. If for
162
Reference Manual
00809-0100-2410, Rev DA
Advanced Configuration