Advanced Configuration
March 2017
C.7

Volume configuration

To configure the Rosemount 2410 Tank Hub for volume calculations, choose one of the standard tank
shapes, or the strapping table option, see
used. For the standard tanks, a Volume Offset parameter can be specified to be used for a non-zero
volume that corresponds to the Zero Level. This may be useful, for example, if you like to include the
product volume below the zero level.
Volume calculation is performed by using a predefined tank shape or a strapping table.
Note
For application software version 1.B5 and older, tank volume calculation has to be enabled in Holding
Register 6136 (see
One of the following standard tank shapes can be chosen:
Sphere
Horizontal Cylinder
Vertical Cylinder
The following parameters must be entered for a standard tank shape:
Tank diameter
Tank length (for horizontal cylinder)
Volume Offset (use this parameter if you like to include product volume below the zero level)
For application software version 1.B5 and older, tank volume calculation has to be enabled by setting
bit 31 "TANK_VOLUME" in Holding Register 6136
C.7.1

Strapping table

The Strapping Table option should be used when the tank shape deviates significantly from an ideal
sphere or cylinder, or when high volume accuracy is required.
The Strapping Table divides the tank into segments. Level values and corresponding volumes are entered
starting at the bottom of the tank. These figures can typically be obtained from tank drawings or from a
certificate provided by the tank manufacturer.
A maximum of 100 strapping points can be entered. For each level value the corresponding total volume
up to the specified level is entered.The volume value is interpolated if the product surface is between
two level values in the table.
148
Table C-4 on page
"Enable volume calculation in a Rosemount 2410 Tank Hub" on page
Reference Manual
00809-0100-2410, Rev DA
149. Select None if volume calculation is not
152).