Reference Manual
00809-0100-2410, Rev DA
C.8.1

Delta Level calculation

The following example illustrates how to use TankMaster WinSetup to configure a Rosemount 2410 to
calculate the difference between product levels for two tanks Tank No. 1 and Tank No. 3. The result is
stored in tank measurement variable Delta_Level in Tank 1.
A Virtual Relay Output can be configured to use the measurement variable Delta_Level as source
parameter to trigger the relay whenever the level difference exceeds a specified value. See
output" on page 140
Figure C-4. Arithmetic operations are configured in Holding Registers 4800 to 4879
Figure C-5. The result is displayed in Input Register 4800 and higher
Advanced Configuration
for more information on how to configure relay functions for a Rosemount 2410.
Advanced Configuration
1. Choose subtraction.
2. Put the result in Tank Measurement Variable
TMV_Delta_Level.
3. Put the result in Tank 1.
Now the result will be stored in
TMV_Delta_Level for Tank 1.
4. For arithmetic operation parameter A
choose Tank Measurement Variable=Level.
5. Choose arithmetic operation parameter A
1
from Tank 1.
2
6. For arithmetic operation parameter B choose
3
Tank Measurement Variable=Level.
4
5
7. Choose arithmetic operation parameter B
6
from Tank 3.
7
The result is displayed in Input
Register 4800.
Parameter A
Parameter B
March 2017
"Relay
155