Service and Troubleshooting
March 2017
Message
Map conflict tank no.
Map conflict TMV type
(TMV=Tank Measurement Variable)
Map conflict device 1
Map conflict device 1 TV no.
(TV=Tank Variable)
Map conflict device 2
Map conflict device 2 TV no.
(TV=Tank Variable)
Internal map conflict
104
Description
Input register no. 6260
Input register no. 6262
0: TMV Level
1: TMV Ullage
2: TMV Level Rate
3: TMV Signal Strength
4: TMV Free Water Level
5: TMV Vapor Pressure
6: TMV Liquid Pressure
7: TMV Air Pressure
8: TMV Ambient Temperature
9: TMV Vapor Avg Temperature
10: TMV Liquid Avg Temperature
11: TMV Tank Avg Temperature
12-27: TMV Temp1 - TMV Temp 16
50: TMV Observed Density
51: TMV Reference Density
52: TMV Flow Rate
53: TMV Tank Volume
54: TMV Tank Height
55: TMV Middle Pressure
56: TMV Delta Level
60-64: TMV USER DEF 1 - 5
Input register no. 6264
Input register no. 6266
TV number 0 - 1019 (Level, Ullage,
Level Rate, Signal Strength etc.)
Input register no. 6268
Input register no. 6270
TV number 0 - 1019 (Level, Ullage,
Level Rate, Signal Strength etc.)
Input register no. 6272
Bit 1: TMV Vapor average
temperature
Bit 2: TMV Liquid average
temperature
Bit 3: TMV Tank average temperature
Bit 4: TMV Observed Density
Bit 5: TMV Reference Density
Bit 6: TMV Tank Volume
Bit 7: Mult TV Map
Bit 8: TMV Internal Map
Bit 9: TMV Arithmetic Value
Reference Manual
00809-0100-2410, Rev DA
Action
Check that tank measurement
variables are mapped to the right
source parameters:
1. In TankMaster Winsetup,
right-click the ATD device icon
associated with the current tank.
2. Click the Properties option.
3. In the 22XX ATD window select the
Advanced Parameter Source
Configuration tab.
Contact Emerson Automation
Solutions/Rosemount Tank Gauging
service department.