Advanced Configuration
March 2017
Enable volume calculation in a Rosemount 2410 Tank Hub
For application software version 1.B5 and older, tank volume calculation has to be enabled by setting bit
31 "TANK_VOLUME" in Holding Register 6136.
1. In the TankMaster Winsetup workspace click the right mouse button on the Rosemount 2410 icon.
2. Choose the View Holding Registers option.
3. Choose Start Register 6136 and click the Read button.
4. For register 6136, double-click the Value field.
5. Scroll down to bit 31. If bit 31=0, double-click the Value field to set bit 31=1.
6. Click OK. In the View Holding Registers window, click the Apply button and close the window.
152
Reference Manual
00809-0100-2410, Rev DA
Advanced Configuration