4. Check the Enable box to activate the Analog Output option.
5. Configure Source Parameter, Value Range, and Alarm Mode as described below.
Tank name/tank position
Choose the tank that will provide the desired measurement data source for the Analog Output. If no tank
name is configured you can check the tank hub's tank database in case you need to verify that the
selected tank position corresponds to the desired tank.
Parameter and value unit
Choose the tank parameter and value unit to associate with the 4 - 20 mA Analog Output.
Value range
Set the source values that correspond to the analog output values 4 mA and 20 mA, respectively. You
can specify any value as long as the 20 mA value is above the 4 mA value. Alarm mode is activated in case
the measurement value goes out of range.
Alarm mode
Alarm mode specifies the analog output state when a measurement error occurs, or when the
measurement value is out of range:
High: the output current is set to 21.75 mA (default setting).
Low: the output current is set to 3.75 mA (default setting).
Freeze current: the output current is set to the present value at the time when the error occurs.
Advanced Configuration
Advanced Configuration
March 2017
157