Advanced Configuration
March 2017
7. Select the desired check box to enable mapping of tank measurement variable to source device and
parameter.
8. Choose the desired tank parameter and value unit. In the example above Vapor Pressure is selected.
9. In Source Device Type column select the appropriate HART device. In the example above, a 3051 PT is
selected.
10.Choose the appropriate source parameter; Hart PV, Hart SV, Hart TV, or Hart QV.
11.In case there are more HART slaves connected, repeat steps
12.In TankMaster WinSetup, install and configure the tank that the HART Slave device was associated
with in the Rosemount 2410 tank database (see step 3).
13.Verify that the tank parameter receives measurement data from the HART Slave by, for example,
opening the Tank View window in TankMaster WinOpi.