Emerson Rosemount 2410 Reference Manual page 111

Tank hub
Hide thumbs Also See for Rosemount 2410:
Table of Contents

Advertisement

Reference Manual
00809-0100-2410, Rev DA
Symptom
The Error LED (red) is
blinking
The Status LED (yellow) is
blinking
Configuration can not be
saved
Rosemount 2410 icon in
TankMaster WinSetup is
red
All measurement values
are indicated with
"SensFail" in the
WinSetup Tank View
window, and with "Error"
in the WinOpi Tank View
window.
Service and Troubleshooting
Possible cause
Various reasons such as hardware or
software failure, communication, or
configuration error
Normal operation. The yellow Status
LED blinks at a constant rate of one
flash every other second.
Write protection switch is set to the
ON position
The Rosemount 2410 is write
protected in TankMaster WinSetup
Application software installed which
is incompatible with current holding
register setup
Corrupt holding registers
Simulation mode active
Map conflict. One or more tank
measurement variables are mapped
to the wrong source parameter. For
example: Vapor Temperature is
mapped to Manual Value.
Service and Troubleshooting
Action
See
"Error messages" on page 69
messages" on page
105.
Check Device Status input register (see
status" on page
102).
See
"LED" on page 70
for more information.
Check write protection switch on the display, see
"Write protection switch" on page
Check write protection in TankMaster WinSetup,
see
"Write protection" on page
Reset holding registers to the default database
setting, see
"Loading the default database" on
page 93
and restart the Rosemount 2410 Tank Hub.
Reset holding registers to the default database
setting, see
"Loading the default database" on
page 93
and restart the Rosemount 2410 Tank Hub.
Stop simulation mode; open WinSetup Set
Simulation Mode window and click the Stop button.
Check diagnostics information (see
on page
84) for possible Device Warning messages:
- in case there is a "Data Manager" warning, check
Input Register 6244
- if register 6244 indicates a "TMV Mapping"
warning check Input Registers 6260 to 6270 for
tank measurement variable mapping conflicts
In TankMaster Winsetup, right-click the ATD device
icon associated with the current tank, and click the
Properties option. In the 22XX ATD window select
the Advanced Parameter Source Configuration tab.
Check that tank measurement variables are
mapped to the right source parameters.
March 2017
and
"Error
"Device
88.
87.
"Diagnostics"
101