the CMA connectors in the reverse order in which you installed them, that is, disconnect
connector D first, then C, then B, and finally A.
Throughout this procedure, once you disconnect any of the CMA's four connectors, do not
allow the CMA to hang under its own weight.
References to "left" or "right" in this procedure assume that you are facing the back of
Note -
the equipment rack.
To reduce the risk of personal injury, stabilize the rack cabinet and extend all anti tilt
Caution -
devices before extending the server from the rack.
Extend all rack anti tilt devices to prevent the rack from tipping over.
1.
For instructions for stabilizing the rack, refer to
Installation
Guide.
Extend the server approximately 13 cm (5 inches) out of the front of the rack, to
2.
make it easier to remove the CMA.
Remove the cables from the CMA.
3.
Disconnect all cables from the rear of the server.
a.
b.
If applicable, remove any additional Velcro straps that were installed to
bundle the cables.
c.
Unwrap the six Velcro straps that are securing the cables.
d.
Open the three cable covers to the fully opened position.
Remove the cables from the CMA and set them aside.
e.
Disconnect connector D.
4.
a.
Press the green release tab (callout 1) on the slide rail latching bracket
toward the left and slide the connector D out of the left slide rail (1 and 2).
When you slide connector D out of the left slide rail, the slide rail latching bracket portion
of the connector remains in place. You will disconnect the connector in the next step.
Remove the Cable Management Arm
"Stabilize the Rack" in SPARC S7-2 Server