Commissioning; Switching On The Transmitter; Enabling Configuration; Post-Installation Check - Endress+Hauser iTEMP TMT162 Operating Instructions Manual

Temperature field transmitter
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

iTEMP TMT162
Endress+Hauser
8

Commissioning

8.1

Post-installation check

Before commissioning the measuring point make sure that all final checks have been
carried out:
• "Post-installation check" checklist, →  12
• "Post-connection check" checklist, →  15
8.2

Switching on the transmitter

Once the final checks have been successfully completed, it is time to switch on the supply
voltage. The transmitter performs a number of internal test functions after power-up. As
this procedure progresses, the following sequence of messages appears on the display:
Step Display
1
"Display" text and firmware version of the display
2
Firm logo
3
Device name (scrolling text)
4
Firmware, hardware version, device version and device address
5
For devices in SIL mode: SIL-CRC is displayed
6a
Current measured value or
6b
Current status message
If the switch-on procedure is not successful, the relevant diagnostic event, depending on the cause,
is displayed. A detailed list of diagnostic events and the corresponding troubleshooting instructions
can be found in the "Diagnostics and troubleshooting" section .
The device operates in normal mode after approx. 30 seconds! Normal measuring mode
commences as soon as the switch-on procedure is completed. Measured values and status
values appear on the display.
8.3

Enabling configuration

If the device is locked and the parameter settings cannot be changed, it must first be
enabled via the hardware or software lock. The device is write-protected if the lock symbol
is shown on the display.
To unlock the device
• either switch the write protection switch on the electronics module to the "OFF" position
(hardware write protection), or
• deactivate the software write protection via the operating tool. See the description for
the 'Define device write protection' parameter. →  83
When hardware write protection is active (write protection switch set to the "ON"
position), write protection cannot be disabled via the operating tool. Hardware write
protection must always be disabled before software write protection can be enabled or
disabled via the operating tool.
Commissioning
33