Operating menu and parameter description

SIL checksum

Navigation
Description

Force safe state

Navigation
Prerequisite:
Description
User entry
Factory setting

Deactivate SIL

Navigation
Description

Restart device

Navigation
Description
Device reset
82
Setup → Advanced setup → SIL → SIL checksum
Displays the calculated SIL checksum.
The SIL checksum displayed can be used to check the device configuration. If 2
devices have identical configurations, the SIL checksum is also identical. This can
make for easy device replacement because if the checksum is the same, the device
configuration is guaranteed to be identical too.
Setup → Advanced setup → SIL → Force safe state
The Operational state parameter displays SIL mode active.
During SIL proof testing this parameter can be used to test error detection of the device
current readback.
• On
• Off
Off
Setup → Advanced setup → SIL → Deactivate SIL
Use this button to quit the SIL operating mode.
Setup → Advanced setup → SIL → Restart device
Use this button to restart the device.
"Administration" submenu