iTEMP TMT162
6.2.3
Access to the operating menu via the operating tool
PROFIBUS® PA functions and device-specific parameters are configured via fieldbus
communication. The following configuration systems, among others, are available for this
purpose:
Operating tools
FieldCare
(Endress+Hauser)
The step-by-step procedure for commissioning the fieldbus functions for the first time is
described in detail in the comprehensive Operating Instructions, as is the configuration
of device-specific parameters.
7
Commissioning
7.1
Function check
Before commissioning the measuring point make sure that all final checks have been carried
out:
• "Post-installation check" checklist, → 11
• "Post-connection check" checklist, → 16
7.2
Switching on the transmitter
Switch on the supply voltage after completing the final checks. The device is ready for
operation after approx. 20 seconds! The transmitter performs a number of internal test
functions after power-up. As this procedure progresses, the following sequence of messages
appears on the local display:
Step
User interface
1
All segments on
2
All segments off
3
Manufacturer data and device name are displayed
4
Current firmware version is displayed
5
Current device revision is displayed
6a
The current measured value is displayed. Bar graph displays the % value within the set bar graph range
6b
The current status message is displayed. If the switch-on procedure fails, the appropriate status message is
displayed, depending on the cause.
If the switch-on procedure is not successful, the relevant diagnostic event, depending on the cause, is
displayed. A detailed list of diagnostic events and the corresponding troubleshooting instructions can
be found in the Operating Instructions.
Endress+Hauser
SIMATIC PDM
(Siemens)
Commissioning
21