Output Current; Failure Mode - Endress+Hauser iTEMP TMT162 Operating Instructions Manual

Temperature field transmitter
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

iTEMP TMT162

Output current

Navigation
Description

Failure mode

Navigation
Description
Additional information
User entry
Endress+Hauser
NOTICE
Current trimming does not affect the digital HART
measured value shown on the display to differ marginally from the value displayed in
the higher-level system.
The digital measured values can be adapted with the sensor trimming parameter in the
menu Expert → Sensor → Sensor trimming.
Procedure
2. Install an accurate ammeter (more accurate than the transmitter) in the current loop.
3. Switch on current output simulation and set the simulation value to 4 mA.
4. Measure the loop current with the ammeter and make a note of the value.
6. Measure the loop current with the ammeter and make a note of the value.
7. Enter the current values determined as adjustment values in the Current trimming 4 mA / 20 mA
Setup → Advanced setup → Current output→ Output current
Use this function to view the calculated output current in mA.
Setup → Advanced setup → Current output→ Failure mode
Expert → Output → Failure mode
Use this function to select the signal on alarm level of the current output in the event of an
error.
If Max. is selected, the signal on alarm level is specified using the Failure current
parameter.
• Min.
• Max.
Operating menu and parameter description
®
value. This can cause the
1. Start
ß
ß
ß
ß
5. Set the simulation value to 20 mA.
ß
ß
parameters
ß
8. End
77

Hide quick links:

Advertisement

Table of Contents
loading