Overview Of Diagnostic Events - Endress+Hauser iTEMP TMT162 Operating Instructions Manual

Temperature field transmitter
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

iTEMP TMT162
Example:
Configuration examples
1. Default setting
2. Manual setting: status
signal S changed to F
3. Manual setting: Warning
diagnostic behavior changed
to Alarm
4. Manual setting: Warning
changed to Disabled
1)
Setting is not relevant.
2)
Status signal is not displayed.
3)
The error current is output if no valid measured value is available.
Endress+Hauser
Diagnostic event and event text
The fault can be identified by means of the diagnostic event. The event text helps you by
providing information on the fault.
Example
If two or more diagnostic events are pending simultaneously, only the diagnostic message
with the highest priority is shown. Additional pending diagnostic messages are shown in
the Diagnostic list submenu →  85. The status signal dictates the priority in which
the diagnostic messages are displayed. The following order of priority applies: F, C, S, M. If
two or more diagnostic events with the same status signal are active simultaneously, the
numerical order of the event number dictates the order of priority in which the events are
displayed, e.g.: F042 appears before F044 and before S044.
Past diagnostic messages that are no longer pending are shown in the Event logbook
submenu→  86.
9.2.2

Overview of diagnostic events

Each diagnostic event is assigned a certain event behavior at the factory. The user can
change this assignment for certain diagnostic events.
Settings
Diagnostic
Status
Diagnostic
number
signal
behavior from
the factory
047
S
Warning
047
F
Warning
047
S
Alarm
1)
047
S
Disabled
The relevant sensor input for these diagnostic events can be identified with the
Actual diag channel parameter or on the display.
Diagnostic event
Status signal
Event number
F
042
3-digit number
Device behavior
Status signal
(output via HART®
communication)
S
F
S
2)
-
Diagnostics and troubleshooting
Event text
Sensor corroded
Current
PV, status
output
Measured
Measured value,
value
UNCERTAIN
Measured
Measured value,
value
UNCERTAIN
Configured
Measured value,
error current
BAD
Last valid
Last valid
measured
measured value,
3)
value
GOOD
Display
S047
F047
S047
S047
37