Endress+Hauser iTEMP TMT162 Operating Instructions Manual page 38

Temperature field transmitter
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

Diagnostics and troubleshooting
Diagnostic
Short text
number
001
Device failure - sensor n
(sensor RJ)
041
Sensor interrupted - sensor n
042
Sensor n corroded
043
Short-circuit sensor n
044
Sensor drift detected
047
Sensor limit reached sensor n
(sensor RJ)
048
Drift detection not possible
062
Sensor connection faulty sensor
n (sensor RJ)
105
Calibration interval
145
Compensation reference point
sensor n
201
Electronics faulty
221
Reference sensor defective
sensor RJ
241
Firmware faulty
242
Firmware incompatible
261
Electronics module defective
283
Memory content inconsistent
286
Data storage inconsistent
401
Factory reset active
402
Initialization active sensor n
(sensor RJ)
38
Corrective measure
Diagnostics for the sensor
3)
1. Restart device
2. Replace electronics
1. Check electrical wiring.
2. Replace sensor.
3. Check connection type.
1. Check sensor.
2. Replace sensor.
1. Check electrical connection.
2. Check sensor.
3. Replace sensor or cable.
1. Check sensor or main electronics.
2. Replace sensor or main electronics.
1. Check sensor.
2. Check process conditions.
1. Check electrical connection.
2. Check sensor.
3. Replace sensor.
Check sensor connection.
1. Execute calibration and reset calibration
interval.
2. Switch off calibration counter.
1. Check terminal temperature.
2. Check external reference point.
Diagnostics for the electronics
1. Restart device.
2. Replace electronics.
Replace device.
1. Restart device.
2. Power cycle device.
3. Replace electronics.
1. Check firmware version.
2. Flash or replace main electronics.
1. Restart device.
2. Replace main electronics module.
1. Restart device.
2. Replace electronics.
1. Repeat safe parameterization.
2. Replace electronics.
Diagnostics for the configuration
Factory reset active, please wait.
Initialization active, please wait.
Diagnosti
Customizable
Status
1)
signal
behavior
from the
from the
factory
factory
Not
customizable
F
Alarm
F
Alarm
M
Warning
F
Alarm
M
Warning
S
Warning
M
Warning
F
Alarm
M
Warning
F
Alarm
F
Alarm
M
Alarm
F
Alarm
F
Alarm
F
Alarm
F
Alarm
F
Alarm
C
Warning
C
Warning
iTEMP TMT162
Customizable
c
2)
Not
customizable
Endress+Hauser

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents