Diagnostics and troubleshooting
36
9.2
Diagnostic events
9.2.1

Displaying diagnostic events

NOTICE
Status signals and diagnostic behavior can be configured manually for certain
diagnostic events. If a diagnostic event occurs, however, it is not guaranteed that the
measured values are valid for the event and comply with the process for the status
signals S and M and the diagnostic behavior: 'Warning' and Disabled'.
Reset the status signal assignment to the factory setting.
Status signals
Symbol
Event
Meaning
category
F
Operating
An operating error has occurred.
error
C
Service mode
The device is in the service mode (during a simulation, for example).
S
Out of
The device is being operated outside its technical specifications (e.g. during
specification
startup or cleaning).
M
Maintenance
Maintenance is required.
required
N
Not
categorized
• If a valid measured value is not available, the display alternates between "- - -- -" and the
error message plus the defined error number and the '' symbol.
• If a valid measured value is present, the display alternates between the status plus the
defined error number (7-segment display) and the primary measured value (PV) with
the '' symbol.
Diagnostic behavior
Alarm
Measurement is interrupted. The signal outputs assume the specified alarm
condition. A diagnostic message is generated.
Warning
The device continues to measure. A diagnostic message is generated.
Disabled
The diagnosis is completely disabled even if the device is not recording a measured
value.
iTEMP TMT162