Operating menu and parameter description
Description
Options
Factory setting

QV

Navigation
Description

Burst mode

Navigation
Description
User entry
Factory setting

Burst command

Navigation
Prerequisite:
Description
108
Use this function to assign a measured variable to the quaternary (fourth) HART value
(QV).
See Assign current output (PV) parameter, →  69
Sensor 1
Expert → Communication → HART output→ QV
Use this function to display the quaternary HART value
"Burst configuration" submenu
Up to 3 burst modes can be configured.
Expert → Communication → Burst configuration → Burst mode
Activation of the HART burst mode for burst message X. Message 1 has the highest
priority, message 2 the second-highest priority, etc.
• Off
The device only sends data to the bus at the request of a HART master
• On
The device regularly sends data to the bus without being requested to do so.
Off
Expert → Communication → Burst configuration → Burst command
This parameter can only be selected if the Burst mode option is enabled.
Use this function to select the command whose answer is sent to the HART master in the
activated burst mode.
iTEMP TMT162
Endress+Hauser