Measured Error For Thermocouples (Tc) And Voltage Transmitters - Endress+Hauser iTEMP TMT162 Operating Instructions Manual

Temperature field transmitter
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

Technische Daten
Standard
Designation
Resistance
Resistance Ω
transmitter
1)
Measured value transmitted via HART
2)
Percentages based on the configured span of the analog output signal.
3)
Maximum measured error for the specified measuring range.
4)
Deviations from maximum measured error due to rounding is possible.

Measured error for thermocouples (TC) and voltage transmitters

Standard
Designation
Type A (30)
IEC 60584-1
Type B (31)
IEC 60584-1 / ASTM
Type C (32)
E988-96
ASTM E988-96
Type D (33)
Type E (34)
Type J (35)
Type K (36)
IEC 60584-1
Type N (37)
Type R (38)
Type S (39)
Type T (40)
Type L (41)
DIN 43710
Type U (42)
GOST R8.8585-2001
Type L (43)
Voltage transmitter
(mV)
1)
Measured value transmitted via HART
2)
Percentages based on the configured span of the analog output signal.
3)
Maximum measured error for the specified measuring range.
4)
Deviations from maximum measured error due to rounding is possible.
52
Measuring range
10 to 400 Ω
10 to 2 000 Ω
®
.
Measuring range
0 to +2 500 °C (+32 to +4 532 °F)
+500 to +1 820 °C
(+932 to +3 308 °F)
0 to +2 000 °C (+32 to +3 632 °F)
–150 to +1 000 °C
(–238 to +1 832 °F)
–150 to +1 200 °C
(–238 to +2 192 °F)
–150 to +1 300 °C
(–238 to +2 372 °F)
+50 to +1 768 °C
(+122 to +3 214 °F)
–150 to +400 °C (–238 to +752 °F)
–150 to +900 °C
(–238 to +1 652 °F)
–150 to +600 °C
(–238 to +1 112 °F)
–200 to +800 °C
(–328 to +1 472 °F)
–20 to +100 mV
®
.
MV = Measured value
LRV = Lower range value of relevant sensor
Measured error (±)
33 mΩ
ME = ± (21 mΩ + 0.003% *
235 mΩ
ME = ± (35 mΩ + 0.010% *
Measured error (±)
1)
Digital
3)
Maximum
Based on measured value
ME = ± (0.08 °C (0.14 °F) +
≤ 1.25 °C (2.25 °F)
0.018% * (MV - LRV))
ME = ± (1.23 °C (2.14 °F) -
≤ 1.23 °C (2.21 °F)
0.05% * (MV - LRV))
ME = ± (0.5 °C (0.9 °F) +
≤ 0.6 °C (1.08 °F)
0.005% * MV - LRV))
ME = ± (0.63 °C (1.13 °F) -
≤ 0.63 °C (1.13 °F)
0.007% * MV - LRV))
ME = ± (0.19 °C (0.3 °F) -
≤ 0.19 °C (0.34 °F)
0.006% * (MV - LRV))
ME = ± (0.23 °C (0.4 °F) -
≤ 0.23 °C (0.41 °F)
0.005% * (MV - LRV))
ME = ± (0.3 °C (0.5 °F) -
≤ 0.30 °C (0.54 °F)
0.002% * (MV - LRV))
ME = ± (0.4 °C (0.7 °F) -
≤ 0.40 °C (0.72 °F)
0.01% * (MV - LRV))
ME = ± (0.95 °C (1.7 °F) -
≤ 0.95 °C (1.71 °F)
0.025% * (MV - LRV))
ME = ± (0.98 °C (1.8 °F) -
≤ 0.98 °C (1.76 °F)
0.02% * (MV - LRV))
ME = ± (0.31 °C (0.56 °F) -
≤ 0.31 °C (0.56 °F)
0.034% * (MV - LRV))
ME = ± (0.26 °C (0.47 °F) -
≤ 0.26 °C (0.47 °F)
0.008% * (MV - LRV))
ME = ± (0.27 °C (0.49 °F) -
≤ 0.27 °C (0.49 °F)
0.022% * (MV - LRV))
ME = ± (2.13 °C (3.83 °F) -
≤ 2.13 °C (3.83 °F)
0.012% * (MV - LRV))
8.9 µV
ME = ± (6.5 µV + 0.002% *
iTEMP TMT162
(MV - LRV))
0.03 % (
4.8 µA)
(MV - LRV))
2)
D/A
4)
0.03 % (
4.8 µA)
4.8 µA
(MV - LRV))
Endress+Hauser