Power Supply - Endress+Hauser iTEMP TMT162 Operating Instructions Manual

Temperature field transmitter
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

iTEMP TMT162
Write protection for device
parameters
Switch-on delay
Supply voltage
Current consumption
Terminals
Cable entries
Cable specification
Residual ripple
Surge arrester
Endress+Hauser
Minimum operating voltage
Multidrop current
Time for connection setup
1)
No Multidrop current in SIL mode
• Hardware: Write protection using DIP switch on electronics module in the device
• Software: Write protection using password
• Until the start of HART
≤ 3.6 mA
• Until the first valid measured value signal is present at the current output, approx. 28 s,
during switch-on delay = I
13.3

Power supply

Values for non-hazardous areas, protected against polarity reversal:
• 11.5 V ≤ Vcc ≤ 42 V (standard)
• I ≤ 23 mA
Values for hazardous areas, see Ex documentation →  61
The transmitter must be powered by an 11.5 to 42 V
with NEC Class 02 (low voltage/low current) with restricted power limited to 8 A/
150 VA in the event of a short-circuit (in accordance with IEC 61010-1, CSA
1010.1-92).
Current consumption
Minimum current consumption
Current limit
2.5 mm
2
(12 AWG) plus ferrule
Version
Type
Thread
2x thread ½" NPT
2x thread M20
2x thread G½"
Cable gland
2x coupling M20
→  17
Perm. residual ripple U
SS
The surge arrester can be ordered as an optional extra. The module protects the electronics
from damage from overvoltage. Overvoltage occurring in signal cables (e.g. 4 to 20 mA,
11.5 V
4.0 mA
• Normal mode: 9 s
• SIL mode: 10 s
®
communication, approx. 10 s, during switch-on delay = I
≤ 3.6 mA
a
3.6 to 23 mA
≤ 3.5 mA, Multidrop mode 4 mA (not possible in SIL mode)
≤23 mA
≤ 3 V at U
≥ 13.5 V, f
b
max.
Technische Daten
AC
1)
power supply in accordance
DC
= 1 kHz
a
49