Access To The Operating Menu Via The Operating Tool; Commissioning; Post-Installation Check; Switching On The Device - Endress+Hauser iTEMP TMT162 Brief Operating Instructions

Temperature field transmitter hart communication
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

Commissioning

6.2

Access to the operating menu via the operating tool

The transmitter and measured value display are configured via the HART
Endress+Hauser Common Data Interface). The following operating tools are available for this
purpose:
Operating tools
FieldCare, DeviceCare, Field Xpert
(Endress+Hauser)
AMS Device Manager
(Emerson Process Management)
The configuration of device-specific parameters is described in detail in the Operating
Instructions for the device.
7
Commissioning
7.1

Post-installation check

Before commissioning the measuring point, make sure that all final checks have been carried
out:
• "Post-mounting check" checklist
• "Post-connection check" checklist
7.2

Switching on the device

Once you have completed the post-connection checks, switch on the supply voltage. The
transmitter performs a number of internal test functions after power-up. During this process,
a sequence containing device information appears on the display.
Step Display
1
Text "Display" and firmware version of the display
2
Firm logo
3
Device name (scrolling text)
4
Firmware, hardware revision, device revision and device address
5
For devices in SIL mode: SIL-CRC is displayed
6a
Current measured value or
6b
Current status message
If the switch-on procedure is not successful, the relevant diagnostic event is displayed, depending on the
cause. A detailed list of diagnostic events and the corresponding troubleshooting instructions can be
found in the Operating Instructions.
22
SIMATIC PDM
(Siemens)
Field Communicator 475
(Emerson Process Management)
iTEMP TMT162
®
protocol or CDI (=
Endress+Hauser