Procedure for setting the DIP switch or activating the proof test:

1. Remove the cover clamp.
2. Unscrew the housing cover together with the O-ring.
3. If necessary, remove the display with the fitting kit from the electronics module.
4. Configure the hardware write protection WRITE LOCK accordingly using the DIP
switch. In general, the following applies: switch to ON = function enabled, switch to
OFF = function disabled.
5. If performing a SIL commissioning test and a proof test, make a device restart using
the button.
Once the hardware setting has been made, re-assemble the housing cover in the reverse
order.
2.
iTEMP TMT162
ON
Pro of-
OF F
Tes t
WR ITE
LOC K
4.
5.
3.
Endress+Hauser
A0033847