Special Connection Instructions; Surge Arrester Function Test - Endress+Hauser iTEMP TMT162 Operating Instructions Manual

Temperature field transmitter
Hide thumbs Also See for iTEMP TMT162:
Table of Contents

Advertisement

iTEMP TMT162
Endress+Hauser
1
2
 9
Shielding and grounding the signal cable at one end with HART® communication
1
Supply unit
2
Grounding point for HART® communication cable shield
3
Grounding of the cable shield at one end
4
Optional grounding of the field device, isolated from cable shielding
5.4

Special connection instructions

If the device is fitted with a surge arrester module, the bus is connected and the power is
supplied via the screw terminals on the surge arrester module.
 10
Electrical connection of surge arrester
5.4.1

Surge arrester function test

NOTICE
To perform the function test on the surge arrester module correctly:
Remove the surge arrester module before performing the test.
To do so, release screws (1) and (2) with a screwdriver as well as securing screw (3)
with an allen key.
The surge arrester module can be lifted off easily.
Perform the function test as shown in the following graphic.
3
Sensor 1
4
5
3
6
S2
-
Bus connection and
supply voltage
4
3
2
1
-
+
4
3
S1
+
+
-
-
-
+
Wiring
A0010984
A0033027-EN
19