iTEMP TMT162

Sensor offset n

Navigation
Description
User entry
Factory setting
Drift/difference mode
Navigation
Description
Additional information
User entry
Factory setting

Drift/difference alarm delay

Navigation
Prerequisite
Endress+Hauser
"Sensor" submenu
n = Stands for the number of sensor inputs (1 and 2)
Setup → Advanced setup → Sensor → Sensor offset n
Expert → Sensor → Sensor n → Sensor offset n
Use this function to set the zero point correction (offset) of the sensor measured value.
The value indicated is added to the measured value.
-10.0 to +10.0
0.0
Setup → Advanced setup → Sensor → Drift/difference mode
Expert → Sensor → Diagnostic settings → Drift/difference mode
Use this function to choose whether the device reacts to the drift/difference limit value
being exceeded or undershot.
Can only be selected for 2-channel operation.
• If the Out band (drift) option is selected, a status signal is displayed if the absolute value
for the differential value exceeds the drift/difference set point
• If the In band option is selected, a status signal is displayed if the absolute value for the
differential value drops below the drift/difference set point.
• Off
• Out band (drift)
• In band
Off
Setup → Advanced setup → Sensor → Drift/difference alarm delay
Expert → Sensor → Diagnostic settings → Drift/difference alarm delay
The Drift/difference mode parameter must be activated with the Out band (drift) or In
band option. →  75