Start Up Procedure For Operation; Table 4-5 Procedure For Starting Up The Controller - Honeywell UDC3200 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

Monitoring and Operating the Controller

4.6 Start Up Procedure for Operation

Table 4-5 Procedure for Starting Up the Controller

Step
Operation
1
Select Manual
Mode
Adjust the Output
2
3
Enter the Local
Setpoint
Select Automatic
4
Mode
Tune the
5
Controller
104
Press
Until "M" indicator is ON.
Man
Man
Man
The controller is in manual mode.
Auto
Auto
Auto
or
To adjust the output value and ensure that the
final control element is functioning correctly.
Upper Display = PV Value
Lower Display = OUT and the output value in %
Upper Display = PV Value
Lower
Lower
Lower
Lower Display = SP and the Local Setpoint
Display
Display
Display
or
To adjust the local setpoint to the value at which
you want the process variable maintained.
The local setpoint cannot be changed if the
Setpoint Ramp function is running.
Until "A" indicator is ON.
Man
Man
Man
The controller is in Automatic mode.
Auto
Auto
Auto
The controller will automatically adjust the output
to maintain the process variable at setpoint.
Make sure the controller has been configured
Setup
Setup
properly and all the values and selections have
been recorded on the Configuration Record
Sheet.
Refer to Tuning Set Up group to ensure that the
selections for PBor GAIN, RATE T, and I MIN, or I
RPM have been entered.
Use Accutune to tune the controller; see the
procedure in this section.
UDC3200 Universal Digital Controller Product Manual
Result
Value
12/04

Advertisement