SPECIFICATIONS

Electrical

Voltage Range: 20-30 VAC; Class 2 transformer Nominal
Power Consumption:
— IP variant: 8VA; Controller and actuator load (nothing
connected to IO's and COM)
— MSTP variant: 6VA; Controller and actuator load (nothing
connected to IO's and COM)
Full Load Power Consumption:
— IP variant: 30VA; Maximum load including external loads
(including SYLK™, communication, BLE, UIO output, 20V output)
— MSTP variant: 22VA; Maximum load including external loads
(including SYLK™, communication, BLE, UIO output, 20V output)
— If SSR is used it should consider real VA needed.
Frequency Range: 50 to 60Hz
Auxiliary Output: 20 VDC @ 75 mA

Hardware

CPU: Crossover processor NXP I.MRT, Cortex M7
Memory capacity: 16MB QSPI Flash, 16MB SDRAM
Ethernet: 2 X RJ-45 Ethernet ports with integrated fail- safe for
daisy-chaining
Real Time Clock: 24-hr backup after power failure. The
controller includes a supercapacitor to power the built-in real
time clock for 24 hours. In case of power failure, the super
capacitor retains the time set in controller for 24 hours. After
24 hours, the time will reset to default factory time until user
perform BACnet Time Sync.

Communication

Protocol supported: BACnet IP (IP variants), BACnet MSTP
(MSTP variants), Sylk™, Modbus Master / Slave (different
order numbers).
Ethernet Connection Speed: 10/100 Mbps
Addressing: IPv4
BACnet Profile: B-AAC
Sylk™ Bus: 2-wire, polarity-insensitive
Bluetooth: BLE, optional external antenna

Airflow Sensor

Range: ±2.0 in. H2O (±500 Pa)
Accuracy: ±3% of full range
Dimension (LXWXH): 175.2 X 154.3 X 90.2 mm (6 8/9
X 6 1/4 X 3 5/7 inch)
Weight: 1.5 Kg
BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION

Operational Environment

Storage: -40 °F to 150 °F (-40 °C to 66 °C)
Operation: 32 °F to 122 °F (0 °C to 50 °C)
Humidity: 5% to 95% RH., non-condensing
protection: IP20, NEMA -1
Pollution: Level2
Sylk™ Devices Supported
Wall Modules Sensors: TR40, TR40-H, TR40-CO2, TR40-H-
CO2, TR42, TR42-H, TR42-CO2, TR42-H-CO2, TR71, TR71-H,
TR75, TR75-H, TR120, TR120-H
Sensors: C7400S Sylk™ Sensor
Universal Input Types and
Characteristics
AO: 0(2)...10V direct/reverse with -3mA ...+20mA (negative
current needed for light dimming) or current output with
0(4)...20mA
UI: 0(2)...10V direct/reverse or 0(4)...20 mA input
Sensors: NTC10k(Type 2), NTC10K3, 10K3A1, NTC20k, PT100,
PT1000, NI1000TK5000, NI1000 Class B DIN43760, PT3000,
JOHNSON A99, 100 Ohm to 100k
Ohm resistive (custom characteristic).
Hardwired wall modules: set point, fan speed, override
Dry contact binary input with direct/reverse
Counter (S0) with 100Hz (min. pulse width 5 ms; e.g. used to
measure fan speed).
Common terminal shared by 2 UIO, protected against 24VAC
mis-wiring and short circuit

Analog Outputs

Output Resolution: 16-bit digital to analog converter
Voltage Output: 0-10 VDC
Current Output: 10-20 mA DC

Solid State Relay

SSR does switch supply voltage, works with AC and DC, however
in case of DC no support of synchronous motor.
1.5A constant; 3.5A inrush for 0.1 sec per SSR output
Optional bridge between 24 VAVC supply and SSR input
shared by all SSRs

Standards and Compliances

CE, UL916 Energy Management Equipment, FCC Part 15; Class
A verified, BTL B-BC, EN 55022; Class A, EN 61000-3-2, 61000,
UL 864 UUKL; Listed Smoke
Control system, UL2043, AMEV AS-A, AMEV AS-B