Figure 2-14 Output #2 - Electromechanical Relay Output; Figure 2-15 Output #2 - Solid State Relay Output - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Load
Supply
Power
1 Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc.
Customer should size fuses accordingly. Use Fast Blo fuses only.
Figure 2-14 Output #2 – Electromechanical Relay Output
See Table 2-6 and Table 2-7 for other information about output types.
Load
Supply
Power
If the load current is less than the minimum rated value of 20 mA, then there may be residual voltage across both
1
ends of the load even if the relay is turned off. Use a dummy resistor as shown to counteract this. The total
current through the resistor and the the load must exceed 20 mA. Solid State Relays are zero-crossing type.
Solid State relays are rated at 1 Amp at 25°C and derated linearly to 0.5 Amp at 55°C. Customer should size
2
fuse accordingly. Use Fast Blo fuses only.
Figure 2-15 Output #2 – Solid State Relay Output
See Table 2-6 and Table 2-7 for other information about output types.
10/05
Relay Load
To terminal
7 (N.C.) or 9 (N.O.)
1
1
Dummy Resistor
Relay Load
2
UDC3500 Universal Digital Controller Product Manual
28
29
L1
30
L2/N
31
4
32
5
33
6
34
7
N.C.
35
8
N.O.
9
36
28
29
L1
30
L2/N
31
4
32
5
6
33
34
7
35
8
N.O.
9
36
Installation
35

Advertisement

Table of Contents