3 Utility Function Mode
3.2.18 Multiturn Limit Value Setting Change When a Multiturn Limit Disagreement Alarm Occurs
(Fn013)
3.2.18 Multiturn Limit Value Setting Change When a Multiturn Limit
Disagreement Alarm Occurs (Fn013)
When the multiturn limit set value is changed with parameter Pn205, a multiturn limit
disagreement alarm (A.CC0) will be displayed because the value differs from that of
the encoder.
If this alarm is displayed, perform the operation described below and change the mul-
titurn limit value in the encoder to the value set in Pn205.
(1)
Preparation
The following condition must be met to clear the alarm and change the multiturn
limit value.
• The write prohibited setting (Fn010) must not be set to write-protect parameters.
(2)
Operating Procedure
Use the following procedure.
Step
Display after Operation
1
2
3
3-42
Alarm
Alarm Name
Display
Multiturn Limit
A.CC0
Disagreement
Alarm
Output
Different multiturn limits have been set in
OFF (H)
the encoder and SERVOPACK.
Keys
Press the
menu for the utility function mode.
Use the
through the list and select Fn013.
Press the
The display changes to the Fn013 exe-
cution display.
Press the
turn limit value. When the setting is
completed, the status display shows
"DONE" for one second. The status
display then returns to show "A.CC0"
again.
Note: If the
instead of the
multiturn limit value will not be
reset.
Meaning
Operation
Key to view the main
or
Key to move
Key.
Key to set the multi-
Key is pressed
Key, the