YASKAWA JUSP-OP05A-1-E User Manual page 81

Ac servo drives
Hide thumbs Also See for JUSP-OP05A-1-E:
Table of Contents

Advertisement

(1)
Preparation
The following conditions must be met to initialize the vibration detection level.
• The write prohibited setting (Fn010) must not be set to write-protect parameters.
• The test without a motor function must be disabled (Pn00C.0 = 0).
(2)
Operating Procedure
Use the following procedure.
Step
Display after Operation
− F U N C T I O N −
R U N
F n 0 1 4 : O p t I n i t
1
F n 0 1 B : V i b l − v l I n i t
F n 0 1 E : S v M o t O p I D
F n 0 1 F : F B O p M o t I D
R U N
V i b r a t i o n D e t e c t
2
L e v e l
S t a r t
: [ D A T A ]
R e t u r n : [ S E T ]
R U N
V i b r a t i o n D e t e c t
3
L e v e l
I n i t
• The vibration may not be detected because of improper
servo gains. Also, not all kinds of vibrations can be
detected. Use the detection result as a guideline.
• Set a proper moment of inertia ratio (Pn103). Improper
setting may result in the vibration alarm, warning misde-
tection, or non-detection.
• The references that are used to operate your system must
be input to execute this function.
• Execute this function under the operating condition for
which the vibration detection level should be set.
• Execute this function while the motor speed reaches at
least 10% of its maximum.
Keys
I n i t
I n i t
Operation
Press the
Key to view the main
menu for the utility function mode.
Use the
or
through the list and select Fn01B.
Press the
Key. The display changes
to the Fn01B execution display.
Press the
Key.
"Init" is displayed flashing, and the vibra-
tion level is detected and initialized.
Note: Continues initialization until the
Key is pressed again.
3.2 Operations
Key to move
9 3
3-47