2: Speed track to restart
then run from the origin speed to the given frequency according to the
acceleration / deceleration time. While the frequency inverter free stops
or instantaneous power cut restarts, regardless it tracks speed to restart
or not, frequency inverter will restart at the speed detected. This
function specially suit for restart after all kinds fault reset.
Attention: When the machine running direction opposite to the output direction,
the speed track to restart function is strictly prohibited to use. It can
not restart until it totally stops. It also can restart by start-up frency
after DC braking.
Tips: In normal FOR/REV swich process or acceletation by frequency setting
change process, it both starts from 0.00Hz or stops to 0.00Hz.
E-31
Power cut restart
selection
E-32
Power cut restart
waiting time
Power cut restart selection:
0: Invalid
While the frequency inverter be electrified after power off, it
must receive the operation order before running.
In the keyboard control or RS485 operational control state, if frequency
inverter power cut, it will automatically clean the operation command.
Frequency inverter detects the motor speed firstly,
range:0,1
Range
: 0.0 ~ 10.0
second
84
Factory
setting:0
Factory
setting:0.5
second