Communication wire must be shield twisted-pair,which is separated from the
control wires. RS485 communication modules are plug-in type installation.
RS485 communication modules plug-in type installation as shown in the following
fig.:
On the right side of the connection terminal in the controlboard, there are
a group of jumper terminals J1, J2 and J3 which is chose to work with software
to decide A02 output mode. Usage details are shown in the following fig.:
Jumper name
Terminal(A02)output selection,when[F-62 set as "0" ,
J1
should J1 short connect,(A02) output pulse frequency.
Terminal(A02)output selection,when[F-62]set as "1"
J2
or"2" ,J2 should short connect, (A02)output 0~20mA as
4~20mA.
Terminal(A02)output selection,when[F-62]set as "3" ,
J3
J3 should short connect, (A02)output 0V~10V.
Details specification