Veichi Electric AC60 series Manual page 123

Table of Contents

Advertisement

This parameter stipulate the counting action of the interior counter, clock
terminal of the counter is selected by the parameter[F-01~F-06].
When the count value to the exterior clock reaches[F-39]setting value,
in the corresponding output terminal, it outputs a valid signal with a width
equal to exterior clock cycle. The output signal stops while the next count
signal is input.
When the count value to the exterior clock reaches[F-40]setting value,
in the corresponding output terminal, it outputs a valid signal. While it
reached [F-39] and the counter clear to zero, this output valid signal
abolishes.
The clock cycle is required to be greater than 3ms; And the minimum pulse
width is 1.5ms.
VS1 terminal input
F-41
voltage lower limit
VS1 terminal input
F-42
voltage upper limit
VS1 terminal input
F-43
voltage gain
Range :0.00V~[F-42]
Range : [F-41] ~10.00V
Range :0.01~5.00
119
Factory
setting:0.00V
Factory
setting:10.00V
Factory
setting:1.00