This parameter stipulate the counting action of the interior counter, clock
terminal of the counter is selected by the parameter[F-01~F-06].
When the count value to the exterior clock reaches[F-39]setting value,
in the corresponding output terminal, it outputs a valid signal with a width
equal to exterior clock cycle. The output signal stops while the next count
signal is input.
When the count value to the exterior clock reaches[F-40]setting value,
in the corresponding output terminal, it outputs a valid signal. While it
reached [F-39] and the counter clear to zero, this output valid signal
abolishes.
The clock cycle is required to be greater than 3ms; And the minimum pulse
width is 1.5ms.
VS1 terminal input
F-41
voltage lower limit
VS1 terminal input
F-42
voltage upper limit
VS1 terminal input
F-43
voltage gain
Range :0.00V~[F-42]
Range : [F-41] ~10.00V
Range :0.01~5.00
119
Factory
setting:0.00V
Factory
setting:10.00V
Factory
setting:1.00