Pid Keyboard Number Given; Feedback Channel Gain; Sensor Maximum Range - Veichi Electric AC60 series Manual

Table of Contents

Advertisement

H-16
PID keyboard number
given
Only when[H-12]setting is"1",this parameter is valid;Take the sensor
largest range[H-18] as a benchmark; When this parameter is changed, PID given
value of monitoring target will automatically synchronize change.
H-17

Feedback channel gain

This function is used to amplify or reduce the input analog quantity of
feedback channel.
H-18

Sensor maximum range

This function is used to adjust the display data of PID given quantity and
PID feedback quantity.
Actual LED display value = given (feedback) signal value - lower input limit
For example, in pressure control, the display value is the actual value of the
pressure while it is set as the maximum pressure of the sensor.
Assume external voltage terminal (VS1) is a feedback signal input channels,
when set (VS1) upper limit voltage as 9V, the lower limit voltage is 0.5V; the
Range :0.0%~100.0%
Range :0.01~5.00
Range :1.0~100.0
upper input limit - input lower limit
136
Factory
setting:50.0%
Factory
setting :1.00
Factory
setting:100.0
×
sensor largest range

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents