Close Down; Signal Cycle (Time By Second) - Veichi Electric AC60 series Manual

Table of Contents

Advertisement

1:Close down
In the process of PID adjustment,while system detectes sensor open circuit,
this parameter is used to choose whether frequency inverter stop working. If
choose working on ,frequency inverter will cancel closed-loop control, with
PID given values as frequency output; If choose close down, when the system
detects the alarm which is mentioned above, the inverter will stop output and
display the malfunction information immediately.
The feedback sensor malfunction is displayed as "SEn". When it detects the PID
feedback quantity is greater than the setting of [H-28], the feedback sensor
fault is deemed to be vanish, and system restores PID closed-loop control
upper
H-30
demarcative value
lower
H-31
demarcative value
PID given quantity is restricted by this parameter in the range of upper、
lower limit demarcative value. this parameter is defined as the ratio of upper、
lower limit demarcative value to maximum range. This function is only valid
in the closed-loop control mode.
H-32
Program running mode

0. Signal cycle (time by second)

While receiving running instructions, the frequency inverter starts
operation from the 1st step speed and direction. The acceleration\deceleration
Rang:
lower
limit
demarcative
100.0%
limit
Rang:0.0%~ upper limit
demarcative value
Range :0 ~ 5
141
limit
Factory
value
setting : 100.0%
Factory
setting :0.0%
Factory
setting:0