VS1 terminal input voltage lower limit
signal the analog input terminal(VS1) receivse. Frequency inverter will
automatically filter the voltage signal whose value is lower than this value.
VS1 terminal input voltage upper limit
signal the analog input terminal(VS1)receives. Frequency inverter will
automatically filter the voltage signal whose value is higher than this value.
VS1 terminal input voltage gain
the (VS1) terminal input analog value.
VS2 terminal input
F-44
voltage lower limit
VS2 terminal input
F-45
voltage upper limit
VS2 terminal input
F-46
voltage gain
VS2 terminal input
F-47
zero offset
VS2 terminal input
F-48
bipolar
adjust
direction control
VS2 terminal input
F-49
bipolar control zero
hysteresis band
VS2 terminal input voltage lower limit
signal which received by the analog input terminal(VS2). Frequency inverter
will automatically filters the voltage signal whose value is lower than this
value.
VS2 terminal input voltage upper limit
signal which received by the analog input terminal(VS2). Frequency inverter
This function defines the minimum
This function defines the maximum
This function is used to amplify or reduce
Range
: -10.00V ~
[F-45]
Range : [F-44] ~10.00V
Range :0.01~5.00
Range :-1.00V~1.00V
and
Range : 0,1,2
Range :0.00V~3.00V
This function defines the minimum
This function defines the maximum
120
Factory
setting:0.00V
Factory
setting:10.00V
Factory
setting:1.00
Factory
setting:0.00V
Factory
setting:0
Factory
setting:0.20V