Veichi Electric AC60 series Manual page 135

Table of Contents

Advertisement

H-01
Free-setting
voltage V1
H-02
Free-setting
frequency F1
H-03
Free-setting
voltage V2
H-04
Free -setting
frequency F2
H-05
Free-setting
voltage V3
H-06
Free-setting
frequency F3
H-07
Free-setting
voltage V4
H-08
Free-setting
frequency F4
H-09
Free-setting
voltage V5
H-10
Free-setting
frequency F5
Free-setting V/F curve:
Users set the 1st / 2nd / 3rd/ 4th / 5th voltage percentage of V / F curves,
base on frequency inverter rated output voltage 100%,corresponding to the
F1/F2/F3/F4/F5 frequency points. Users set the 1st / 2nd / 3rd/ 4th / 5th
frequency values of V / F curves, corresponding to the V1/V2/V3/V4/V5.
Range:0.0%~[H-03]
Range:0.00Hz~[H-04]
Range: [H-01~H-05]
Range: [H-02~H-06]
Range: [H-03~H-07]
Range: [H-04~H-08]
Range: [H-05~H-09]
Range: [H-06~H-10]
Range: [H-07]~100.0%
Range :[ H-08 ] ~ maximum
frequency
131
Factory setting:
0.0%
Factory setting:
0.00Hz
Factory setting:
25.0%
Factory setting:
12.50Hz
Factory setting:
50.0%
Factory setting:
25.00Hz
Factory setting:
75.0%
Factory setting:
37.50Hz
Factory setting:
100.0%
Factory setting:
50.00Hz