frequency compensation amount should base on motor rated slip; The
compensation value should not be set too high.
E-23
Energy
saving
selection
0:Invalid
1:Valid
In operation, inverter can auto-calculate the best output voltage to load
according to the load condition to save the electricity. Electricity saving
function works by reducing output voltage, enhancing the power factor and motor
efficiency.
E-24
Voltage automatic
regulation
0:Invalid
1:Omnidistance valid
2:Only invalid in deceleration
The output voltage automatic control function is the AVR function. When
the AVR function is invalid, the output voltage changes along with the input
voltage change. When AVR function is valid, so long as minimum value of the
input voltage undulation is higher than the output voltage setting (motor rated
voltage), it enables the output voltage maintaining the setting value. When
the voltage supply is lower than the rated output voltage, the output voltage
will reduce along with the input voltage drops.
E-25
Jog frequency
E-26
Jog
acceleration
time
E-27
Jog
deceleration
time
operation
Range :0,1
Range :0,1,2
Range:0.00Hz~upper limit
frequency
Range:0.1~6500.0 second
Range:0.1~6500.0 second
81
Factory
setting:0
Factory
setting:0
Factory setting:
5.00Hz
Factory setting:
2.0 second
Factory setting:
2.0 second