Set the nameplate parameters of the motor under controlled. Pls set the
parameters strictly according to the nameplate. Or the machine can not work
normally.
E-60
Inverter output
voltage ratio
It is the ratio of frequency inverter output voltage to frequency inverter
rated output voltage. This function is used to adjust the output voltage of
the frequency inverter, in order to meet need of V/F characteristic.
Frequency inverter output voltage=frequency inverter rated output voltage
×frequency output voltage ratio
E-61

G/P modules setting

When reset the factory setting, this parameter setting values will not be
changed.
0:G model,suitable for constant torque load.
1:P model, suitable for variable torque(such as fan、water pump load).
The AC60 series frequency inverter adopts G/P in one mode. The power of
the motor adaptor used in the constant torque load (G model) is one level lower
than that used in fan、water pump load(P model).
E-62
Speed
tracking
stability
time
This parameter is defied as the stable operation time while the frequency
Range :50%~100%
Range :0 ,1
Range: 0.20~10.00second
99
Factory
setting:100%
Factory
setting:0
Factory
setting:0.60
second