Table 4.1 Required and Optional Constant Settings (Continued)
Constant
Category
Number
FSDrive-MX1S
o2-04
Capacity Selection

Control Method Settings

Autotuning methods depend on the control method set for the Matrix converter. Make the settings as required
by the control method used.
Control Method Selection
Either of the following two control methods can be selected.
Control Method Constant Setting
Open-loop vector
A1-02 = 2
control
Flux vector
A1-02 = 3
control
(Factory setting)

Turning on the Medium-voltage Power Supply

Items to be checked before turning on the medium-voltage power supply:
Confirm that the power supply voltage is correct.
Confirm that the Matrix converter main circuit terminals (input terminals R, S, and T and output terminals
U, V, and W) are correctly connected.
Make sure that the motor is not connected to a mechanical system (No-load status).
Items to be checked after turning on the medium voltage power supply:
Measure the input voltage of each power cell.
If the input voltage exceeds the power cell rated input voltage of 630 VAC, switch the transformer tap set-
ting for main circuit and recheck the input voltage.
DANGER
Use the Digital Operator to confirm the input power supply voltage U1-90.
Confirm that the Digital Operator displays the Matrix converter as being in normal status.
Name
The code indicating the FSDrive-MX1S
capacity is set before shipment. Normally, the
initial setting can be left unchanged. Confirm
the setting in Advanced Programming Mode.
Basic Control
Current vector control
without a PG
Current vector control
with a PG
This job must be performed by a person qualified for high-voltage work. There is considerable
risk of electrical shock.
: Required constant settings,
Description
60 to FF
Main Applications
Variable speed control that requires high performance
without using a PG
Ultra high-performance control using a PG such as
high-accuracy speed control, torque control, and torque
limit
Trial Operation Procedures