Snubber over-current detected
This trip indicates that an over-current condition has been detected in the rectifier snubbing circuit, The exact cause of the
trip can be identified by the sub-trip number.
Source
Power
system
92
Recommended actions:
Ensure the internal EMC filter is installed
Ensure the motor cable length does not exceed the maximum for selected switching frequency
Check for supply voltage imbalance
Check for supply disturbance such as notching from a DC drive
Check the motor and motor cable insulation with an insulation tester.
Install a output line reactor or sinusoidal filter
OI.SC
Output phase short-circuit
Over-current detected on drive output when enabled. Possible motor earth fault.
Recommended actions:
228
Check for short circuit on the output cabling
Check integrity of the motor insulation using an insulation tester
Is the motor cable length within limits for the frame size?
Out.P
Output phase loss detected
The Out.P trip indicates that phase loss has been detected at the drive output.
Sub-trip
98
NOTE
If Pr 05.042 = 1, the physical output phases are reversed, and so sub-trip 3 refers to physical output phase V and sub-trip 2
refers to physical output phase W.
Recommended actions:
Check motor and drive connections
To disable the trip set Output Phase Loss Detection Enable (06.059) = 0
140
Electrical
Getting
Basic
installation
started
parameters
xx
y
01
1
1
U phase detected as disconnected when drive enabled to run.
2
V phase detected as disconnected when drive enabled to run.
3
W phase detected as disconnected when drive enabled to run.
The drive output frequency is above 4 Hz and a phase is disconnected for the time
4
specified by Output Phase Loss Detection Time (06.058).
Running the
NV Media
Optimization
motor
Card
Diagnosis
zz
00
Rectifier snubber over-current trip detected.
Reason
Onboard
Advanced
Diagnostics
PLC
parameters
Description
Unidrive M200 / M201 Control User Guide