Nidec Digistart D3 User Manual

Nidec Digistart D3 User Manual

23 a - 1600 a / 200 v - 690 v

Advertisement

Digistart D3
23 A - 1600A
200 V - 690 V

Advertisement

Table of Contents
loading

Summary of Contents for Nidec Digistart D3

  • Page 1 Digistart D3 23 A - 1600A 200 V - 690 V...
  • Page 2 If there is any doubt, please contact Nidec or your local Distributor. Environmental Statement Nidec is committed to minimising the impacts of its manufacturing operations. To this end, we operate an Environmental Management System (EMS) which is certified to the International Standard ISO 14001.
  • Page 3: Table Of Contents

    Quick setup details ............................58 Standard menu ..............................59 Advanced menu ..............................60 Parameter Descriptions ............................ 65 Maintenance Tools ............................86 Diagnostics ..............................91 Protection Responses ............................91 Trip Messages ..............................91 General Faults ..............................95 Digistart D3: User Guide Issue: G...
  • Page 4 UL Compliant Installation ..........................110 Maintenance ..............................111 12.1 Care ................................111 12.2 Measuring the motor current ........................... 111 12.3 Measuring the input and output power ......................111 12.4 Exchanging products ............................111 Options ................................112 Digistart D3: User Guide Issue: G...
  • Page 5: Safety Information

    The values of the motor parameters set in the starter affect the protection of the motor. The default values in the starter should not be relied upon. It is essential that the correct value is entered in Pr 1A Motor Full Load Current. This affects the thermal protection of the motor. Digistart D3: User Guide Issue: G...
  • Page 6: Adjusting Parameters

    (e.g. a latching relay). 1.7.6 Short circuit The Digistart D3 is not short circuit proof. After severe overload or short circuit, the operation of the Digistart D3 should be fully tested by an authorised service agent.
  • Page 7: Rating Data

    380 ~ 690 VAC (± 10%) - grounded star supply system only CAUTION Digistart D3 can only be used on 690V IT supply equipped with surge protectors. Please contact Nidec or your local distributor. Current Ratings Contact your local supplier for ratings under operating conditions not covered by these ratings charts.
  • Page 8 1000 A 936 A 796 A 664 A D3-1200-N 1200 A 1200 A 1200 A 1071 A D3-1410-N 1410 A 1410 A 1319 A 1114 A D3-1600-N 1600 A 1600 A 1600 A 1353 A Digistart D3: User Guide Issue: G...
  • Page 9 1500 A 1404 A 1194 A 997 A D3-1200-N 1800 A 1800 A 1800 A 1606 A D3-1410-N 2115 A 2115 A 1979 A 1671 A D3-1600-N 2400 A 2400 A 2400 A 2030 A Digistart D3: User Guide Issue: G...
  • Page 10 1395 A 1395 A 1200 A 966 A D3-1200-N 1800 A 1800 A 1702 A 1474 A D3-1410-N 2115 A 2033 A 1780 A 1535 A D3-1600-N 2400 A 2400 A 2149 A 1840 A Digistart D3: User Guide Issue: G...
  • Page 11 790 A 661 A 527 A D3-0930-N 930 A 751 A 597 A D3-1200-N 1200 A 1148 A 932 A D3-1410-N 1410 A 1200 A 979 A D3-1600-N 1600 A 1444 A 1181 A Digistart D3: User Guide Issue: G...
  • Page 12 1185 A 991 A 790 A D3-0930-N 1395 A 1126 A 895 A D3-1200-N 1800 A 1722 A 1398 A D3-1410-N 2115 A 1800 A 1468 A D3-1600-N 2400 A 2166 A 1771 A Digistart D3: User Guide Issue: G...
  • Page 13 2.2.4 Minimum and Maximum Current Settings The Digistart D3's minimum and maximum full load current settings depend on the model: In-line connection Inside delta connection Model Minimum Maximum Minimum Maximum D3-0023-B 23 A 34 A D3-0043-B 43 A 64 A...
  • Page 14: Mechanical Installation

    Mechanical Installation WARNING Digistart D3 models D3-0145-B to D3-1600-N weigh in excess of 15 kg (33 lb). Use appropriate safeguards when lifting these models. WARNING Models D3-0145-B to D3-1000-B and D3-0255-N to D3-1600-N are intended to be mounted in an enclosure which prevents access except by trained and authorised personnel, and which prevents the ingress of contamination.
  • Page 15: Dimensions And Weights

    (19.7) (34.8) (28.6) (14.2) (5.2) (5.1) (0.2) (0.3) (308.7) NOTE Dimensions F, G and H are the additional space required for the output and input busbars, in addition to the overall chassis measurement (C). Digistart D3: User Guide Issue: G...
  • Page 16 3.1.1 Bypassed Models (D3-0023-B~D3-1000-B) D3-0023-B, D3-0043-B, D3-0050-B, D3-0053-B, D3-0145-B, D3-0170-B, D3-0200-B, D3-0220-B D3-0076-B, D3-0097-B, D3-0100-B, D3-0105-B D3-0255-B, D3-0350-B, D3-0425-B D3-0500-B, D3-0580-B, D3-0700-B, D3-0820-B, D3-0920-B, D3-1000-B Digistart D3: User Guide Issue: G...
  • Page 17 3.1.2 Non-bypassed Models (D3-0255-N~D3-1600-N) D3-0255-N D3-0360-N, D3-0380-N, D3-0430-N, D3-0620-N, D3-0650-N, D3-0790-N, D3-0930-N, D3-1200-N, D3-1410-N, D3-1600-N Digistart D3: User Guide Issue: G...
  • Page 18: Physical Installation

    Soft starters may be mounted side by side with no clearance (that is, if mounted without communications modules). The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%. Digistart D3: User Guide Issue: G...
  • Page 19: Busbar Adjustment Procedure

    The busbars on non-bypassed models D3-0360-N ~ D3-1600-N can be adjusted for top or bottom input and output as required. CAUTION It is the user's responsibility to follow these instructions correctly. Nidec cannot be held responsible for any damage to the starter or associated equipment from incorrect practice. Input/Output...
  • Page 20 CTs to the bracket. For models D3-0360-N ~ D3-0930-N, the CTs must be placed on an angle (the left hand legs of each CT will be on the top row of holes and the right hand legs will be on the bottom tabs). Digistart D3: User Guide Issue: G...
  • Page 21: Electrical Installation

    The bypass terminals are T1B, T2B, T3B. 1/L1 3/L2 5/L3 R e a d y R u n T ri p L o ca l L C L Re se t R MT 2/T1 4/T2 6/T3 Digistart D3: User Guide Issue: G...
  • Page 22 28 mm 6 mm 13 mm 32 mm 32 mm D3-0360-N~D3-0930-N D3-1200-N~D3-1600-N 38 Nm (28.0 ft-lb) 66 Nm (48.7 ft-lb) 12.5 mm 10.5 mm (M12) (M10) 51 mm 16 mm 32 mm 13 mm Digistart D3: User Guide Issue: G...
  • Page 23 (supplementary insulation) rated for use at the AC supply voltage. Control terminations use 2.5mm plug-in terminal blocks. Unplug each block, complete the wiring, then reinsert the block. 220~440 VAC 110~210 VAC Digistart D3: User Guide Issue: G...
  • Page 24 4.1.5 Start/Stop control logic The Digistart D3 has three fixed inputs for remote control. These inputs should be controlled by contacts rated for low voltage, low current operation (gold flash or similar). The maximum cable run is determined by the type of cable used, provided the maximum resistance of this cable does not exceed 100 Ohms.
  • Page 25 4.1.7 Motor Thermistors Motor thermistors can be connected directly to the Digistart D3. The soft starter will trip when the resistance of the thermistor circuit exceeds approximately 3.6 kΩ or falls below 20 Ω. If no motor thermistors are connected to the Digistart D3 thermistor input terminals TH1, TH2 must be open. If TH1, TH2 are shorted, the Digistart D3 will trip.
  • Page 26: Control Connections

    COM4, RLC4, RLO4 Relay output C The Digistart D3 can be disabled via the control inputs. An open circuit across DI4, +24V will disable the starter. The Digistart D3 will not respond to start commands. If running, the soft starter will allow the motor to coast to stop, ignoring the soft stop mode set in Pr 2H.
  • Page 27: Power Connections

    The Digistart D3 can be connected to the motor in-line or inside delta (also called three-wire and six-wire connection). When connecting in inside delta, enter the motor full load current (FLC) for Pr 1A. The Digistart D3 will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
  • Page 28 In-line installation, externally bypassed Non-bypassed models have dedicated bypass terminals, which allow the Digistart D3 to continue providing protection and monitoring functions even when bypassed via an external bypass contactor. The bypass contactor must be connected to the bypass terminals and controlled by the soft starter's run output (terminals COM2, RLO2).
  • Page 29 NOTE When connecting in inside delta, enter the motor full load current (FLC) for Pr 1A. The Digistart D3 will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
  • Page 30 Inside delta installation, externally bypassed Non-bypassed models have dedicated bypass terminals, which allow the Digistart D3 to continue providing protection and monitoring functions even when bypassed via an external bypass contactor. The bypass contactor must be connected to the bypass terminals and controlled by the soft starter's run output (terminals COM2, RLO2).
  • Page 31: Fuse Information

    HRC fuses (such as Ferraz/Mersen AJT fuses) can be used for Type 1 coordination according to IEC 60947-4-2 standard. NOTE Fuses are not delivered with Digistart D3 soft starters. CAUTION Adaptive Control controls the motor's speed profile, within the programmed time limit. This may result in a higher level of current than traditional control methods.
  • Page 32 170M6014 D3-0790-N 2530000 170M6017 170M6017 170M6016 D3-0930-N 4500000 170M6019 170M6019 170M6019 D3-1200-N 4500000 170M6021 –– –– D3-1410-N 6480000 –– –– –– D3-1600-N 12500000 170M6019* –– –– * Two parallel connected fuses required per phase. Digistart D3: User Guide Issue: G...
  • Page 33 –– D3-0790-N 2530000 –– –– –– D3-0930-N 4500000 –– –– –– D3-1200-N 4500000 –– –– –– D3-1410-N 6480000 –– –– –– D3-1600-N 12500000 –– –– –– * Two parallel connected fuses required per phase. Digistart D3: User Guide Issue: G...
  • Page 34 D3-0620-N 1200000 D3-0650-N 1200000 D3-0790-N 2530000 Not suitable Not suitable D3-0930-N 4500000 D3-1200-N 4500000 D3-1410-N 6480000 D3-1600-N 12500000 * Two parallel connected fuses required per phase. ** Two series connected fuses required per phase. Digistart D3: User Guide Issue: G...
  • Page 35 D3-0790-N 2530000 A070URD33XXX1400 A070URD33XXX1400 A070URD33XXX1250 D3-0930-N 4500000 A070URD33XXX1400 A070URD33XXX1400 A070URD33XXX1400 D3-1200-N 4500000 A055URD33XXX2250 –– –– D3-1410-N 6480000 A055URD33XXX2250 –– –– D3-1600-N 12500000 –– –– –– XXX = blade type. See Ferraz/Mersen catalog for details. Digistart D3: User Guide Issue: G...
  • Page 36 D3-0790-N 2530000 6.6URD33XXXX1400 6.6URD33XXXX1400 –– D3-0930-N 4500000 6.6URD33XXXX1400 6.6URD33XXXX1400 –– D3-1200-N 4500000 6URD233PLAF2200 6URD233PLAF2200 –– D3-1410-N 6480000 6URD233PLAF2200 6URD233PLAF2200 –– D3-1600-N 12500000 6URD233PLAF2800 6URD233PLAF2800 –– XXX = blade type. See Ferraz/Mersen catalog for details. Digistart D3: User Guide Issue: G...
  • Page 37 A4BQ800 A4BQ800 D3-0650-N 1200000 A4BQ800 A4BQ800 D3-0790-N 2530000 A4BQ1200 A4BQ1200 D3-0930-N 4500000 A4BQ1200 / A4BT1100 A4BQ1200 / A4BT1100 D3-1200-N 4500000 A4BQ1600 A4BQ1600 D3-1410-N 6480000 A4BQ2000 A4BQ2000 D3-1600-N 12500000 A4BQ2500 / A4BT1800 A4BQ2500 / A4BT1800 Digistart D3: User Guide Issue: G...
  • Page 38 For UL compliant installation, select a fuse that meets the specified fuse class and maximum fuse rating. 600 VAC circuits • For UL compliant installation, the starter can be protect by either fuses or a circuit breaker as specified in the following tables. Digistart D3: User Guide Issue: G...
  • Page 39 † - Models provided with a “3 cycle rating” are suitable for use in a circuit with the prospective current noted, when protected by any UL Listed fuses or UL Listed circuit breakers sized according to the NEC. Digistart D3: User Guide Issue: G...
  • Page 40 65 kA Not suitable UTS800HU/ 30 kA UTS1200HU (1200) D3-0620-N SGLA36AT800 (1200) UTS800/ UTS1200 D3-0650-N (1200) 42 kA D3-0790-N SKLA36AT1200 D3-0930-N (1200) UTS1200 (1200) D3-1200-N D3-1410-N 85 kA Siemens: HPX3R1600 (1600) 85 kA D3-1600-N Digistart D3: User Guide Issue: G...
  • Page 41 I t less than the I t of the soft starter SCRs. When selecting semiconductor fuses for Digistart D3, use the I t values in the table. For further information on selecting semiconductor fuses, contact your local distributor.
  • Page 42: Bypass Contactor

    Main Contactor A main contactor must be installed if the Digistart D3 is connected to the motor in inside delta format and is optional for in-line connection. Select a contactor with an AC3 rating greater than or equal to the full load current rating of the connected motor.
  • Page 43: Keypad And Status

    The keypad can be removed from the soft starter and mounted remotely on a panel using the remote mounting kit. The keypad stores a backup copy of the parameters in the soft starter, so one keypad can be used to program multiple Digistart D3 starters. NOTE The keypad can be removed or replaced while the starter is running.
  • Page 44: Synchronising The Keypad And The Starter

    The retaining tabs on the back of the faceplate will snap into place. Synchronising the Keypad and the Starter When a keypad is connected to a Digistart D3, it synchronises its parameter settings with the settings in the soft starter.
  • Page 45 5.4.3 Programmable screen The Digistart D3's user-programmable screen can be configured to show the most important information for the particular application. Use Pr 9B to 9E to select which information to display. 000.0A 0.0pf 00000hrs 000kWh 5.4.4 Current The current screen shows real-time line current on each phase. If the RTD/PT100 and ground fault protection card is fitted, the screen will also show ground current.
  • Page 46: Quick Start Commissioning

    • control supply connections (terminals CSH, CSL, CSR depending on the control voltage) • programmable input A (DI4, +24V) must be closed or Pr 3A Input A Function must be changed from Starter Disable Digistart D3: User Guide Issue: G...
  • Page 47: Setup Procedure

    • Program parameters The Quick Setup Menu makes it easy to configure the Digistart D3 for common applications. The Digistart D3 selects the parameters relevant to the application and suggests a typical setting, and you can adjust each parameter to suit your exact requirements.
  • Page 48: Operation

    • The Remote LED on the Digistart D3 is on when the soft starter is in Remote mode and off when in Local mode. The Remote LED is located on the main body of the starter (behind the keypad) and is only visible if the keypad is remotely mounted.
  • Page 49 100% Time 7.2.3 Adaptive Control for Starting In an adaptive control soft start, the Digistart D3 adjusts the current in order to start the motor within a specified time and using a selected acceleration profile. CAUTION Adaptive Control cannot start the motor faster than a direct on-line (DOL) start. If the start ramp time (Pr 2D) is shorter than the motor's DOL start time, starting current may reach DOL levels.
  • Page 50 Set a start Current Limit (Pr 2B) sufficiently high to allow a successful start. The first Adaptive Control start will be a Constant Current start. This allows the Digistart D3 to learn the characteristics of the connected motor. This motor data is used by the Digistart D3 during subsequent Adaptive Control starts.
  • Page 51: Stop Methods

    7.3.1 Coast to Stop Coast to stop lets the motor slow at its natural rate, with no control from the soft starter. The time required to stop will depend on the type of load. Digistart D3: User Guide Issue: G...
  • Page 52 7.3.3 Adaptive Control for Stopping In an adaptive control soft stop, the Digistart D3 controls the current in order to stop the motor within a specified time and using a selected deceleration profile. Adaptive Control can be useful in extending the stopping time of low inertia loads.
  • Page 53 The first Adaptive Control stop will be a normal soft stop. This allows the Digistart D3 to learn the characteristics of the connected motor. This motor data is used by the Digistart D3 during subsequent Adaptive Control stops.
  • Page 54 DC braking when the motor stops. This avoids unnecessary heating of the motor. For more information on using the Digistart D3 with an external speed sensor (eg for applications with variable load during the braking cycle), see DC Brake with External Zero Speed Sensor on page 102.
  • Page 55: Jog Operation

    Do not disable current imbalance protection (Pr 5C) during inside delta operation. NOTE When connecting in inside delta, enter the motor full load current (FLC) for Pr 1A. The Digistart D3 will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
  • Page 56: Programming

    Pr 1B, 1C and 1D are suitable for most applications. Consult the motor datasheet before changing these settings. Programming Menu The Programming Menu lets you view and change programmable parameters that control how the Digistart D3 operates. To open the Programming Menu, press the M button while viewing the monitoring screens.
  • Page 57: Access Code

    At the confirmation prompt, select YES to confirm or NO to cancel and Load Defaults then M to load/save the selection. When the action has been completed, the screen will briefly display a confirmation message, then return to the status screens. Digistart D3: User Guide Issue: G...
  • Page 58: Quick Setup Details

    To access the Quick Setup Menu, press the M button and select Quick Setup Menu. The Quick Setup Menu makes it easy to configure the Digistart D3 for common applications. The Digistart D3 selects the parameters relevant to the application and suggests a typical setting, and you can adjust each parameter to suit your exact requirements.
  • Page 59: Standard Menu

    00:00 (minutes:seconds) Relay C Action Trip Relay C On Delay 00:00 (minutes:seconds) Relay C Off Delay 00:00 (minutes:seconds) 5 - Protection Settings Excess Start Time 00:20 (minutes:seconds) Phase Sequence Any Sequence Underpower Overpower 400% Digistart D3: User Guide Issue: G...
  • Page 60: Advanced Menu

    F2 Button Action None Display A or kW Current Advanced menu The Advanced Menu gives access to all the programmable parameters in the Digistart D3. See Parameter Descriptions on page 65. Parameter Group Parameters Default Value 1 - Primary Motor Settings...
  • Page 61 Do Not Check 6 - Protection Delays Current Imbalance Delay 00:03 (minutes:seconds) Underpower Delay 00:05 (minutes:seconds) Overpower Delay 00:00 (minutes:seconds) Reserved Reserved Frequency Delay 00:01 (minutes:seconds) Restart Delay 00:10 (minutes:seconds) Ground Fault Delay 00:03 (minutes:seconds) Digistart D3: User Guide Issue: G...
  • Page 62 00:05 (minutes:seconds) Reset Delay Group C 5 minutes 11 - Secondary Motor Motor FLC-2 Model dependent Settings Dual Thermal Model Single Locked Rotor Current-2 600% Locked Rotor Time-2 00:10 (minutes:seconds) Motor Service Factor-2 105% Digistart D3: User Guide Issue: G...
  • Page 63 50 °C RTD/PT100 F °C 50 °C RTD/PT100 G °C 50 °C 15 - Restricted Access Code 0000 Emergency Run Disable Adjustment Lock Read & Write Shorted SCR Action 3-Phase Control Only Jog Torque Digistart D3: User Guide Issue: G...
  • Page 64 Trip Starter RTD/PT100 A Trip Starter RTD/PT100 B Trip Starter RTD/PT100 C Trip Starter RTD/PT100 D Trip Starter RTD/PT100 E Trip Starter RTD/PT100 F Trip Starter RTD/PT100 G Trip Starter Low Control Volts Trip Starter Digistart D3: User Guide Issue: G...
  • Page 65: Parameter Descriptions

    Ground Fault and PT100 inputs B ~ G are only available if RTD/PT100 B the RTD/PT100 and ground fault protection card has been RTD/PT100 C installed. RTD/PT100 D RTD/PT100 E RTD/PT100 F RTD/PT100 G Digistart D3: User Guide Issue: G...
  • Page 66 When connecting in inside delta, enter the motor full load current (FLC) for Pr 1A. The Digistart D3 will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
  • Page 67 5%~10%. If the motor speed fluctuates during starting or stopping, decrease the gain setting slightly. 2M – Brake Torque Range: 20% - 100% Default: Description: Sets the amount of brake torque the Digistart D3 will use to slow the motor. Digistart D3: User Guide Issue: G...
  • Page 68 Pr 2N is used in conjunction with Pr 2I. See Brake on page 54 for details. Auto-start and auto-stop The Digistart D3 can be programmed to start and stop automatically, after a specified delay or at a specified time of day. Auto-start and auto-stop can be set separately. Auto-start/stop is only available in Remote mode.
  • Page 69 8.8.4 Group 3 - Digital Inputs The Digistart D3 has two programmable inputs, which allow remote control of the soft starter. If required, two extra inputs are available on the input/output expansion card. 3A – Input A Function Options: Motor Set Select The Digistart D3 can be configured with two separate sets of motor data.
  • Page 70 3N – Remote Reset Logic Options: Normally Closed (default) Normally Open Description: Selects whether the Digistart D3's remote reset input (terminals DI3, +24V) is normally open or normally closed. 3O – Comms in Remote Options: Disable Control in RMT Enable Control in RMT (default)
  • Page 71 8.8.5 Group 4 - Digital Outputs The Digistart D3 has three programmable outputs, which can be used to signal different operating conditions to associated equipment. Three additional outputs are available on the input/output expansion card. 4A - Relay A Action Options: Relay A is not used.
  • Page 72 Heatsink overtemperature Motor Temperature Flag Phase Loss Input A trip Motor thermistor Input B trip Changeover Contactor Description: Selects the function of Relay E (normally open). See Pr 4A Relay A Action for details. Digistart D3: User Guide Issue: G...
  • Page 73 5A, 5B – Excess Start Time Excess start time is the maximum time the Digistart D3 will attempt to start the motor. If the motor does not transition to Run mode within the programmed limit, the starter will trip. Set for a period slightly longer than required for a normal healthy start.
  • Page 74 Sets the trip point for ground fault protection. The Digistart D3 can be configured to trip if ground fault exceeds a specified level while the motor is running. Ground fault is a dynamic trip based on phase current measurements every half-cycle.
  • Page 75 7A – Low Current Flag The Digistart D3 has low and high current flags to give early warning of abnormal operation. The current flags can be configured to indicate an abnormal current level during operation, between the normal operating level and the undercurrent or instantaneous overcurrent trip levels.
  • Page 76 If required, a second analog output and an analog input are available on the input/output expansion card. 8A – Analog Input Trip An analog input can be fitted to the Digistart D3 if required. An external device can activate the analog input to trip the soft starter in response to external conditions.
  • Page 77 Calibrates the lower limit of the analog output to match the signal measured on an external current measuring device. 8.8.10 Group 9 - Display 9A - Languages Options: English Deutsch Français Español Italiano Chinese Description: Selects which language the keypad will use to display messages and feedback. Digistart D3: User Guide Issue: G...
  • Page 78 9E User Screen - Bottom Right Default: kWh 9F – Graph Data The Digistart D3 has a real-time performance graph to report the behaviour of critical operating parameters. Options: Current (% FLC) (default) Current as a percentage of motor full load current.
  • Page 79 8.8.11 Group 10 - Auto-Reset The Digistart D3 can be programmed to automatically reset certain trips, which can help minimise operating downtime. Trips are divided into three categories for auto-reset, depending on the risk to the soft starter:...
  • Page 80 Pr 11A to 12N to suit the second motor. • To use the Digistart D3 with two different motor data sets for the same motor (for dual speed motors or applications where starting conditions may vary), use Pr 11B to select a single thermal model, and configure the starting and stopping profiles as required in Pr 12A to 12N.
  • Page 81 12E – Adaptive Start Profile-2 Options: Early Acceleration Constant Acceleration (default) Late Acceleration Description: Selects which profile the Digistart D3 will use for an Adaptive Control soft start. 12F – Kickstart Level-2 Range: 100% - 700% FLC Default: 500% Description: Sets the level of the kickstart current.
  • Page 82 Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control. 12M – Brake Torque-2 Range: 20% - 100% Default: Description: Sets the amount of brake torque the Digistart D3 will use to slow the motor. 12N – Brake Time-2 Range: 1 - 30 (seconds) Default: 1 second Description: Sets the duration for DC injection during a braking stop.
  • Page 83 8.8.15 Group 14 - RTD/PT100 The Digistart D3 has one RTD/PT100 input and can be fitted with another six PT100 inputs by using the RTD/PT100 and ground fault protection card. The inputs can trip the soft starter when the temperature exceeds a specified point, and different trip temperatures can be set for each input.
  • Page 84 If PowerThrough is enabled, Pr 2C and 2B must be set appropriately. 15E – Jog Torque The Digistart D3 can jog the motor at a reduced speed, which allows precise positioning of belts and flywheels. Jog can be used for either forward or reverse operation.
  • Page 85 Ground Fault • 16Q: RTD/PT100 A • 16R: RTD/PT100 B • 16S: RTD/PT100 C • 16T: RTD/PT100 D 16U: • RTD/PT100 E • 16V: RTD/PT100 F • 16W: RTD/PT100 G • 16X: Low Control Volts Digistart D3: User Guide Issue: G...
  • Page 86: Maintenance Tools

    The soft starter's thermal modelling software constantly monitors the motor's performance. This allows the starter to calculate the motor's temperature and ability to start successfully at any time. If the Digistart D3 is configured for use on two motors, each motor's temperature is modelled separately.
  • Page 87 Run Simulation Scroll to Run Simulation and press M. Ready Apply Start Signal Press START or activate the start input. The Digistart D3 simulates its Run Simulation pre-start checks and closes the main contactor relay. The Run LED Pre-Start Checks flashes.
  • Page 88 Testing the Installation The Digistart D3 can be connected to a small motor for testing. During this test, the soft starter's control input and relay output protection settings can be tested. This test mode is not suitable for testing soft starting or soft stopping performance.
  • Page 89 Scroll to Event Log and press M. Use the buttons to select an event to view, and press M to display details. To close the log and return to the main display, press repeatedly. Digistart D3: User Guide Issue: G...
  • Page 90 Press M to view details. Use the To reset a counter, press M then press M to confirm the action. To return to the previous level, press NOTE The reset counters function is protected by the access code. Digistart D3: User Guide Issue: G...
  • Page 91: Diagnostics

    Unauthorised tampering with the unit will void the product warranty. Protection Responses When a protection condition is detected, the Digistart D3 will write this to the event log and may also trip or issue a warning. The soft starter's response depends on the Protection Action setting (parameter group 16).
  • Page 92 Check for other equipment in the area that could be affecting the mains supply, particularly variable speed drives and switch mode power supplies (SMPS). If the Digistart D3 is connected to a generator set supply, the generator may be too small or could have a speed regulation problem.
  • Page 93 PowerThrough will not operate if control power is cycled between starts. Related Pr: 15D The Digistart D3 has detected a drop in the internal control voltage. Low Control Volts Check the external control supply (CSH, CSL, CSR) and reset the starter.
  • Page 94 A short circuit has occurred. Check and resolve this condition. • Related Pr: None The Digistart D3 is internally bypassed and has drawn high current during running. (The 10A Time-overcurrent protection curve trip has been reached or the motor current has risen to 600% of the motor FLC setting.)
  • Page 95: General Faults

    The starter may be disabled via a programmable input. If Pr 3A or 3F is • set to Starter Disable and there is an open circuit on the corresponding input, the Digistart D3 will not start. If there is no further need to disable the starter, close the circuit on the input. NOTE Pr 3M Local/Remote controls when the LCL/RMT button is enabled.
  • Page 96 The load may be jammed. Check the load for severe overloading or a locked rotor situation. Erratic motor operation. The SCRs in the Digistart D3 require at least 5 A of current to latch. If • you are testing the soft starter on a motor with full load current less than 5 A, the SCRs may not latch correctly.
  • Page 97: Application Examples

    10.1 Installation with Main Contactor The Digistart D3 is installed with a main contactor (AC3 rated). Control voltage must be supplied from the input side of the contactor. The main contactor is controlled by the Digistart D3 Main Contactor output, which by default is assigned to Output Relay A (terminals COM1, RLO1).
  • Page 98: Installation With External Bypass Contactor

    10.2 Installation with External Bypass Contactor The Digistart D3 is installed with an external bypass contactor (AC1 rated). The bypass contactor is controlled by the Digistart D3 Run Output (terminals COM2, RLO2). Control voltage Remote control inputs Motor thermistor input...
  • Page 99: Emergency Run Operation

    10.3 Emergency Run Operation In normal operation the Digistart D3 is controlled via a remote two-wire signal (terminals DI2, +24V). Emergency Run is controlled by a two-wire circuit connected to Input A (terminals DI4, +24V). Closing Input A causes the Digistart D3 to run the motor and ignore certain trip conditions.
  • Page 100: Auxiliary Trip Circuit

    Auxiliary Trip Circuit In normal operation the Digistart D3 is controlled via a remote two-wire signal (terminals DI2, +24V). Input A (terminals DI4, +24V) is connected to an external trip circuit (such as a low pressure alarm switch for a pumping system).
  • Page 101 Set at around 120 seconds. Limits operation of the input trip to 120 seconds after the start signal. This allows time for pressure to build up in the piping before the low pressure input becomes active. Digistart D3: User Guide Issue: G...
  • Page 102: Dc Brake With External Zero Speed Sensor

    DI4, +24V will open and the starter will be disabled. When the next start command is given (ie next application of K10), DI4, +24V closes and the Digistart D3 is enabled. The Digistart D3 must be operated in remote mode and Pr 3A Input A Function must be set to 'Starter Disable'. CAUTION If the brake torque is set too high, the motor will stop before the end of the brake time and the motor will suffer unnecessary heating which could result in damage.
  • Page 103 When using DC brake, the mains supply must be connected to the soft starter (input terminals L1, L2, L3) in positive phase sequence and Pr 5D Phase Sequence must be set to Positive Only. Digistart D3: User Guide Issue: G...
  • Page 104: Soft Braking

    When the Digistart D3 receives a stop signal (pushbutton S2), it opens the forward run contactor (K1) and closes the braking contactor (K2) after a delay of approximately 2-3 seconds (K1T). K12 is also closed to activate the secondary motor settings, which should be user programmed for the desired stopping performance characteristics.
  • Page 105: Two-Speed Motor

    10.7 Two-Speed Motor The Digistart D3 can be configured for control of dual speed Dahlander type motors, using a high speed contactor (K1), low speed contactor (K2) and a star contactor (K3). NOTE Pole Amplitude Modulated (PAM) motors alter the speed by effectively changing the stator frequency using external winding configuration.
  • Page 106: Slip-Ring Motor

    10.8 Slip-Ring Motor The Digistart D3 can be used to control a slip-ring motor, using rotor resistance. Control voltage Remote control 1/L1 2/T1 inputs Motor thermistor 3/L2 4/T2 input RTD/PT100 input 24 VDC output 5/L3 6/T3 Relay outputs Analog output...
  • Page 107 10.8.1 Commissioning Configure the Digistart D3 as follows: Parameter settings: • Pr 4D Relay B Action • Select 'Changeover contactor' • Pr 4E Relay B On Delay • Set this to the maximum time (5m:00s). • Pr 13A Motor Data-1 Ramp •...
  • Page 108: Technical Data

    Analog output (AO1, 0V) ................... 0-20 mA or 4-20 mA (selectable) Maximum load ......................600 Ω (12 VDC @ 20 mA) Accuracy ................................. ± 5% 24 VDC output (+24V, 0V) Maximum load ............................. 200 mA Accuracy ..............................± 10% Digistart D3: User Guide Issue: G...
  • Page 109 D3-0023-B ~ D3-0105-B ....................... 1,000,000 operations D3-0145-B ~ D3-1000-B ........................100,000 operations CAUTION D3-0220-B~D3-1000-B: The contacts on the internal bypass contactors should be checked for wear after the stated number of operations. Periodic servicing/replacements may be required. Digistart D3: User Guide Issue: G...
  • Page 110: Ul Compliant Installation

    11.1 UL Compliant Installation This section details additional requirements and configuration settings for the Digistart D3 to be UL-compliant. See also UL Short Circuit Ratings on page 38. 11.1.1 Models D3-0023-B ~ D3-0105-B There is no additional requirement for these models.
  • Page 111: Maintenance

    Protective covers must remain in place during tests. There are very few maintenance and repair operations for the user to perform on Digistart D3 soft starters. Regular servicing operations and simple methods for checking that the starter is operating correctly are described below.
  • Page 112: Options

    Starter status monitoring (Ready, Starting, Running, Stopping, Tripped) • Performance monitoring (motor current, motor temperature) To use Digistart-Soft with the Digistart D3, the soft starter must be fitted with a Modbus or USB Module. Digistart D3 - Finger Guard Finger guards may be specified for personnel safety. Finger guards fit over the soft starter terminals to prevent accidental contact with live terminals.