Trip
C.OPt
NV Media Card trip; option module installed is different between source drive and destination drive
The C.OPt trip indicates that parameter data is being transferred from the NV Media Card to the drive, but the option
module category is different between the source and destination drives. This trip does not stop the data transfer, but is a
warning that the data for the option module that is different will be set to the default values and not the values from the card.
This trip also applies if a compare is performed between the data block on the card and the drive, and the option module
fitted is different between the source and target.
180
Recommended actions:
Ensure the correct option module is installed.
Press the red reset button to acknowledge that the parameters for the option module installed will be at their
default values
This trip can be suppressed by setting Pr 00 to 9666 and resetting the drive.
C.Pr
NV Media Card data blocks are not compatible with the drive derivative
The C.Pr trip is initiated either at power-up or when the card is accessed, If Drive Derivative (11.028) or Product Type
(11.063) are different between the source and target drives. This trip can be reset and data can be transferred in either
direction between the drive and the card.
Sub-trip
175
Recommended actions:
Use a different NV Media Card
This trip can be suppressed by setting Pr 00 to 9666 and resetting the drive
Choose a file compatible between the source and target drives, if sub-trip 2.
C.rdo
NV Media Card has the Read Only bit set
The C.rdo trip indicates that an attempt has been made to modify data on a read-only NV Media Card or to modify a read-
only data block. A NV Media Card is read-only if the read-only flag has been set.
181
Recommended actions:
Clear the read only flag by setting Pr 00 to 9777 and reset the drive. This will clear the read-only flag for all data blocks
in the NV Media Card
C.rtg
NV Media Card Trip; The voltage and / or current rating of the source and destination drives are different
The C.rtg trip indicates that parameter data is being transferred from the NV Media Card to the drive, but the current and /
or voltage ratings are different between source and destination drives. This trip also applies if a compare (using Pr 00 set to
8yyy) is performed between the data block on a NV Media Card and the drive. The C.rtg trip does not stop the data transfer
but is a warning that rating specific parameters with the RA attribute may not be transferred to the destination drive.
186
Recommended actions:
Reset the drive to clear the trip
Ensure that the drive rating dependent parameters have transferred correctly
This trip can be suppressed by setting Pr 00 to 9666 and resetting the drive.
C.SL
NV Media Card trip; Option module file transfer has failed
The C.SL trip is initiated, if the transfer of an option module file to or from a module failed because the option module does
174
not respond correctly. If this happens this trip is produced with the sub-trip number indicating the option module slot
number.
C.tyP
NV Media Card parameter set not compatible with current drive mode
The C.tyP trip is produced during a compare if the drive mode in the data block on the NV Media Card is different from the
current drive mode. This trip is also produced if an attempt is made to transfer parameters from a NV Media Card to the
drive if the operating mode in the data block is outside the allowed range of operating modes, for the target drive.
Recommended actions:
187
Ensure the destination drive supports the drive operating mode in the parameter file.
Clear the value in Pr 00 and reset the drive
Ensure destination drive operating mode is the same as the source parameter file
Unidrive M200 / M201 Control User Guide
Issue Number: 2
Electrical
Getting
Basic
installation
started
parameters
If Drive Derivative (11.028) is different between the source and target drives. This trip is initiated either
1
at power-up or when the SD card is accessed. This trip can be reset and data can be transferred in
either direction between the drive and the card.
If Product Type (11.063) is different between the source and target drives or the file is corrupted or
2
incompatible. This trip is initiated either at power-up or when the SD card is accessed. This trip can be
reset but no data are transferred in either direction between the drive and the card.
Running the
NV Media
Optimization
motor
Card
Diagnosis
Reason
Onboard
Advanced
Diagnostics
PLC
parameters
UL Listing
131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive m201

Table of Contents