Oht.P
Power stage over temperature
This trip indicates that a power stage over-temperature has been detected. From the sub-trip 'xxyzz', the Thermistor
location is identified by 'zz'.
Power system
22
Recommended actions:
Check enclosure / drive fans are still functioning correctly
Force the heatsink fans to run at maximum speed
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Reduce the drive switching frequency
Reduce duty cycle
Increase acceleration / deceleration rates
Use S ramp (Pr 02.006)
Reduce motor load
Check the derating tables and confirm the drive is correctly sized for the application.
Use a drive with larger current / power rating
OI.A1
Analog input 1 over-current
189
Current input on analog input 1 exceeds 24mA.
OI.AC
Instantaneous output over current detected
The instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX. This trip cannot be reset until 10s
after the trip was initiated.
Recommended actions/checks:
Increase acceleration/deceleration rate
If seen during autotune reduce the voltage boost
3
Check for short circuit on the output cabling
Check integrity of the motor insulation using an insulation tester
Is the motor cable length within limits for the frame size?
Reduce the values in the frequency loop gain parameters - (Pr 03.010, 03.011, 03.012) or (Pr 03.013, 03.014, 03.015)
Reduce the values in the current loop gain parameters
OI.br
Braking IGBT over current detected: short circuit protection for the braking IGBT activated
The OI.br trip indicates that over current has been detected in braking IGBT or braking IGBT protection has been activated.
This trip cannot be reset until 10s after the trip was initiated.
Recommended actions:
4
Check brake resistor wiring
Check braking resistor value is greater than or equal to the minimum resistance value
Check braking resistor insulation
Unidrive M200 / M201 Control User Guide
Issue Number: 2
Electrical
Getting
Basic
installation
started
parameters
Source
xx
01
Drive size
1 to 4
5
06200XXX
06400XXX
06500XXX
Running the
NV Media
Optimization
motor
Diagnosis
y
zz
0
zz
Thermistor location in the drive defined by zz
Trip temperature (°C)
95
115
115
125
120
Onboard
Advanced
Diagnostics
Card
PLC
parameters
Description
Trip reset temperature (°C)
90
110
110
120
115
UL Listing
139