Oh.dc
DC bus over temperature
The Oh.dc trip indicates a DC bus component over temperature based on a software thermal model. The drive includes a
thermal protection system to protect the DC bus components within the drive. This includes the effects of the output current
and DC bus ripple. The estimated temperature is displayed as a percentage of the trip level in Pr 07.035. If this parameter
reaches 100 % then an Oh.dc trip is initiated. The drive will attempt to stop the motor before tripping. If the motor does not
stop in 10 seconds the drive trips immediately.
Control system
Recommended actions:
Check the AC supply voltage balance and levels
27
Check DC bus ripple level
Reduce duty cycle
Reduce motor load
Check the output current stability. If unstable;
Oht.C
Control stage over-temperature
This trip indicates that a control stage over-temperature has been detected if Cooling Fan control (06.045) = 0.
This trip causes the option module to go to standby and Potential Drive Damage Conditions (10.106) bit 1 to be set.
219
Recommended actions:
Increase ventilation by setting Cooling Fan control (06.045) > 0.
Oht.I
Inverter over temperature based on thermal model
This trip indicates that an IGBT junction over-temperature has been detected based on a software thermal model.The Oht.I
trip is initiated when the temperature based on the thermal model reaches 145 C. The trip reset temperature is 139 C
Control system
Recommended actions:
21
Reduce the selected drive switching frequency
Ensure Auto-switching Frequency Change Disable (05.035) is set to OFF
Reduce duty cycle
Increase acceleration / deceleration rates
Reduce motor load
Check DC bus ripple
Ensure all three input phases are present and balanced
138
Electrical
Getting
Basic
installation
started
parameters
Source
xx
00
Check the motor map settings with motor nameplate (Pr 05.006, Pr 05.007, Pr 05.008, Pr 05.009, Pr 05.010,
Pr 05.011) – (All Modes)
Disable slip compensation (Pr 05.027 = 0) – (Open loop)
Disable dynamic V to F operation (Pr 05.013 = 0) - (Open loop)
Select fixed boost (Pr 05.014 = Fixed) – (Open loop)
Select high stability space vector modulation (Pr 05.019 = 1) – (Open loop)
Disconnect the load and complete a rotating autotune (Pr 05.012)
Reduce frequency loop gains (Pr 03.010, Pr 03.011, Pr 03.012) – (RFC-A)
Source
xx
00
Running the
NV Media
Optimization
motor
Diagnosis
y
zz
2
00
DC bus thermal model gives trip with sub-trip 0
y
zz
1
00
Inverter thermal model gives {Oht.I} trip with sub-trip 100
Onboard
Advanced
Diagnostics
Card
PLC
parameters
Description
Description
Unidrive M200 / M201 Control User Guide
UL Listing