Appendix D MSG-SND/ MSG-RCV Functions (Ethernet)
D.2 Message Receive Function (MSG-RCV)
D.2.5 Function Setting and Parameter Details for MELSEC Protocol
This section explains the MSG-RCV function setting and its parameter list details when MELSEC is used as a protocol.
( 1 ) Message Receive Function Setting
[ a ] 218IFA/218IFC Setting Example
An example of a function setting when 218IFA/218IFC is used as a transmission device follows:
Set the protocol type to MEMOBUS when used in MELSEC protocol.
Set the circuit number in accordance with the circuit number allocated to the target 218IFA/218IFC.
Set a unique communication buffer channel number for the same circuit.
For information on the register number, refer to D.2.2 ( 1 ) Input Item and D.2.2 ( 2 ) Output Item.
Communication device = 218IFA/2181FC
Communication buffer channel number = 1
[ b ] 218IF Setting Example
An example of a function setting when 218IF is used as a communication device follows:
Set the protocol type to MEMOBUS when used in MELSEC protocol.
Set the circuit number in accordance with the circuit number allocated to the target 218IF.
Set a unique communication buffer channel number for the same circuit.
For information on the register number, refer to D.2.2 ( 1 ) Input Item and D.2.2 ( 2 ) Output Item.
Communication buffer channel number = 1
( 2 ) Process Result (PARAM00)
Refer to D.2.4 ( 2 ) Process Result (PARAM00).
( 3 ) Status (PARAM01)
Refer to D.2.4 ( 3 ) Status (PARAM01).
( 4 ) Connection Number (PARAM02)
Refer to D.2.4 ( 4 ) Connection Number (PARAM02).
A-66
Protocol = MEMOBUS
Circuit number = 1
Parameter list start address = DA00000
(use DW00000-DW00016)
Communication device = 218IF
Protocol = MEMOBUS
Circuit number = 1
Parameter list start address = DA00000
(use DW00000-DW00016)
MSG-RCV
DB000201
Execute
Busy
DB000202
Complete
Abort
Dev-Typ
00016
Error
00001
Pro-Typ
00001
Cir-No
00001
Ch-No
Param
DA00000
MSG-RCV
DB000201
Execute
Busy
DB000202
Complete
Abort
Dev-Typ
00006
Error
Pro-Typ
00001
00001
Cir-No
00001
Ch-No
Param
DA00000
DB000210
DB000211
DB000212
DB000210
DB000211
DB000212