6.3 Communication with Touch Panel
6.3.1 When CPU-03/CPU-04 Acts as Slave (automatic receive function is used)
Setting Example
The following figure shows an example which displays the content of the CPU-03/CPU-04 (slave) holding regis-
ter (MW00100) on a touch panel and writes values from the touch panel to the same register.
CPU-03/CPU-04
YASKAWA
Holding register (M register)
The setup procedure is explained in the following pages.
6-64
Slave
(Local station)
IP address: 192.168.001.001
Port number: 10001
CPU-03/CPU-04
(Local station)
MW00100
Communication Protocol
Extended MEMOBUS
Type
protocol
Connection Type
TCP
BIN
Data Code Type
Ethernet
Read
Write
Master
Touch Panel
(Remote station)
IP address: 192.168.001.002
Port number: 10001
Touch panel
GP3000 series
(Remote station)
GMW00100