Appendix D MSG-SND/ MSG-RCV Functions (Ethernet)
D.1 Message Send Function (MSG-SND)
( 7 ) Data Address (PARAM05)
Specify the start address of the data.
The address must be input in decimal or hexadecimal numbers.
Example: When the start address is MW01000, specify "1000 (decimal)" or "3E8H (hexadecimal)."
The valid range of usable function codes and data addresses may differ, depending on the device type and device range
of the MELSEC side.
The following table gives the valid ranges of data addresses when using MELSEC as a protocol.
Device
X
Y
M
M
B
F
TS
TC
CS
CC
M
Device
TN
CN
D
D
(special)
W
R
D
Note: 1. The device range may differ according to the MELSEC sequencer even within the device range. For
more information, refer to the MELSEC manual.
2. The register number corresponding to MP200 can be adjusted by the offset setting of the MSG-SND
function.
A-36
Table D.7 Valid Range of Data Addresses (MELSEC bit device)
Device Range of
Decimal/
ACPU Common
Hexa-
Commands
decimal
X0000 to X07FF
Hexadecimal 02H: Input relay
Y0000 to Y07FF
Hexadecimal 01H/0FH: Coil
M0000 to M2047
Decimal
M9000 to M9255
Decimal
B0000 to B03FF
Hexadecimal 01H/05H/0FH: Coil
F0000 to F0255
Decimal
TS000 to TS255
Decimal
TC000 to TC255
Decimal
CS000 to CS255
Decimal
CC000 to CC255
Decimal
M2048 to M8191
Decimal
Table D.8 Valid Range of Data Addresses (MELSEC word device)
Device Range of
Decimal/
ACPU Common
Hexa-
Commands
decimal
TN000 to TN255
Decimal
CN000 to CN255
Decimal
D0000 to D1023
Decimal
D9000 to D9255
Decimal
W0000 to W03FF
Hexadecimal
R0000 to R8191
Decimal
D1024 to D6143
Decimal
Valid Range of
Function Code
Data Addresses
0 to 2047
0 to 2047
2048 to 4095
01H/05H/0FH: Coil
4096 to 4351
01H/05H/0FH: Coil
4352 to 5375
5376 to 631
01H/05H/0FH: Coil
2048 to 2303
02H: Input relay
2304 to 2559
02H: Input relay
2560 to 2815
02H: Input relay
2816 to 3071
02H: Input relay
8192 to 14335
01H/05H/0FH: Coil
Valid Range of
Function Code
Data Addresses
04H/0AH:
0 to 255
Input register
04H/0AH:
256 to 511
Input register
03H/06H/09H/0BH/
0 to 1023
0EH/10H:
Holding register
03H/06H/09H/0BH/
1024 to 1279
0EH/10H:
Holding register
03H/06H/09H/0BH/
1280 to 2303
0EH/10H:
Holding register
03H/06H/09H/0BH/
2304 to 10495
0EH/10H:
Holding register
03H/06H/09H/0BH/
10496 to 15615
0EH/10H:
Holding register
Corresponding Register
Number
MB000000 to MB00127F
MB000000 to MB00127F
MB001280 to MB00255F
MB002560 to MB00271F
MB002720 to MB00335F
MB003360 to MB00351F
MB001280 to MB00143F
MB001440 to MB00159F
MB001660 to MB00175F
MB001760 to MB00191F
MB005120 to MB00895F
Corresponding Register
Number
MW00000 to MW0255
MW00256 to MW00511
MW00000 to MW01023
MW01024 to MW01279
MW01280 to MW02303
MW02304 to MW10495
MW10496 to MW15615