YASKAWA MP2200 User Manual page 325

Machine controller
Hide thumbs Also See for MP2200:
Table of Contents

Advertisement

8.2 Troubleshooting
8.2.4 Troubleshooting System Errors
( 3 ) Troubleshooting Flowchart for System Errors
A troubleshooting flowchart for system errors is provided below.
START
Use the LED indicator
pattern
*
to classify the
error.
Battery alarm
indicator
BAT lit?
Classifications = Warning
ALM indicator lit or
blinking?
Classifications = Fatal error
ERR indicator blinking?
Hardware failure/watchdog timeout error
Only ERR indicator lit?
Turn OFF the STOP switch on
DIP switch SW6 and turn ON the
power.
Online Stop Mode
Only RDY indicator lit?
Check SW00050.
Watchdog timeout error?
User program
error
User program error
Check the location of the error
referring to 8.2.4 ( 4 ) Correcting
User Program Errors.
*
For LED indicator pattern, refer to 8.2.3 ( 2 ) LED Indicator Meanings.
8-10
YES
Replace battery.
NO
YES
Alarm
NO
YES
Fatal error
NO
NO
YES
NO
YES
Check if more than one EXIOIF
Module is mounted to one Rack.
NO
YES
NO
Using EXIOIF Module?
YES
(1) Operation error (SB000418)
(2) I/O error (SB000419)
Hardware
failure
Check CPU Error Status (SW00041).
Refer to 8.2.4 ( 5 ) [ c ] Ladder Program User
Operation Error Status.
Refer to 8.2.4 ( 5 ) [ e ] System I/O Error Status.