6.2 Communication with Other MP Series
6.2.4 When the CPU-03/CPU-04 Acts as Master (ladder program which uses MSG-SND function)
4.
Set a communication setting in the Message Communication Easy Setting Dialog Box.
How to set up in the Message Communication Easy Setting Dialog Box
 When automatic receive function is used, select "3" for the Connect No.
 Set Port No. of the CPU-03/CPU-04 side ("10003," for example).
 Select Extended MEMOBUS for Communication protocol Type, and click the Default Button.
 Select Connect Type (TCP, for example).
 Select Code (BIN, for example).
 Set Node Port IP Address of the other device (MP2300) to be connected ("192.168.001.002," for example).
 Set Port No. of the other device (MP2300) to be connected ("10003," for example).
 Click OK.
 Caution
When message functions (MSG-SND, MSG-RCV) are used with the connection number 01, disable the automatic receive func-
tion. If message functions are used while the automatic receive function is enabled, the communication will not function prop-
erly.
Note: The automatic receive function with a connection number 01 is set to "Enable" by default.
6-50