Application Selection; Setting 1: Water Supply Pump Application; Setting 2: Conveyor Application - YASKAWA A1000 Series Technical Manual

High performance vector control drive models: 200 v class: 0.4 to 110 kw 400 v class: 0.4 to 355 kw
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

4.6

Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals, and sets certain parameters to
values appropriate for the application that was selected. In addition, the parameters most likely to be changed are
assigned to the group of User Parameters, A2-01 through A2-16. User Parameters are part of the Setup Group, and
provide quicker access to by eliminating the need to scroll through multiple menus.
An Application Preset can either be selected from the Application Selection display in the Setup Group
Simplified Setup Using the Setup Group on page
Note: An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to
initialize the drive by setting A1-03 to "2220" or "3330" prior to selecting an Application Preset.
WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change
the I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.
No.
A1-06
Application Presets

◆ Setting 1: Water Supply Pump Application

No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Duty Rating
E1-03
V/f Pattern Selection
E1-07
Mid Output Frequency
E1-08
Mid Output Frequency Voltage
L2-01
Momentary Power Loss Operation Selection
L3-04
Stall Prevention Selection during Deceleration
Table 4.6 Water Supply Pump: User Parameters (A2-01 to A2-16)
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
E1-03
V/f Pattern Selection
E1-07
Mid Output Frequency

◆ Setting 2: Conveyor Application

No.
A1-02
Control Method Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Duty Rating
L3-04
Stall Prevention Selection during Deceleration
YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
95) or in parameter A1-06. The following presets can be selected:
Parameter Name
Table 4.5 Water Supply Pump: Parameter Settings
Name
Parameter Name
Table 4.7 Conveyor: Parameter Settings
Parameter Name
Setting Range
0: Disabled
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
6: Hoist
7: Crane
Default Setting
0: V/f Control
1: Reverse Prohibited
1.0 s
1.0 s
1: Normal Duty
0FH
30.0 Hz
50.0 V
1: Enabled
1: Enabled
No.
E1-08
Mid Output Frequency Voltage
E2-01
Motor Rated Current
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
L5-01
Number of Auto Restart Attempts
Default Setting
0: V/f Control
3.0 s
3.0 s
0: Heavy Duty
1: Enabled
4.6 Application Selection
(Refer to
Default
0
Parameter Name
4
103