2. PROGRAMMING OUTPUTS (MOD AND RELAY) WITH NO RESET

2. PROGRAMMING OUTPUTS (MOD
AND RELAY) WITH NO RESET
The T775U can be programmed for Reset or No Reset.
From the factory, the T775U is programmed for No Reset.
This section describes the steps necessary to program
the controller for No Reset.
MENU
PROGRAM
Fig. 57. Program Menu.
PROGRAM
MOD 1
Fig. 58. Program Menu - No Reset.
PROGRAM
MOD 1

SETPOINT

Fig. 59. Program - Setpoint.
MENU
PROGRAM
MOD 1
MOD 2
RELAY 1
RELAY 2
EXIT
M24567
MENU
PROGRAM
MOD 1
SETPOINT
SETBACK
SENSOR
THROT RNG
ACTION
EXIT
M24580A
MENU
PROGRAM
MOD 1
SETPOINT
70
o
F
ENTER
SETPOINT
FOR
MOD 1
M24581
T775U SERIES 2000 CONTROLLER
NOTE: For applications where Reset is not used, only
one sensor (Sensor A) is available for use.

2.1. Entering Program Mode

Press the MENU button, then select PROGRAM and
press the
button to view the Program menu.

2.1.1. Program Menu for Outputs with No Reset

From the Program menu, select MOD 1, MOD 2,
RELAY 1, or RELAY 2 to view the parameters. This
section illustrates the screens for selecting MOD 1, but
other than as noted below, the programming is the same
for each output.
NOTE: For Relays, DIFFRNTL replaces THROT RNG.
NOTE: The Setback parameter displays only if schedul-
ing is enabled (see Fig. 47 on page 21) or the DI
Option is set to Setback. (see Fig. 49 on
page 22).
Continue with "2.1.2. SETPOINT".
2.1.2. SETPOINT
1. From the menu, use the
light SETPOINT.
2. Press the
button to display the setpoint value.
3. Use the
and
desired setpoint temperature.
Default: 70°F (21°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the
button to accept the setpoint tempera-
ture and display the next option.
25
and
buttons to high-
buttons to increase/decrease the
62-0255–05